Owner's manual
Supplemental Drive Information A-5
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P
Carrier Frequency
For Frame 2 drives, see the carrier frequency derating table below.
PowerFlex 700L Frame 3A and 3B drives cannot be run above 4 kHz.
Horsepower/Current
Ratings
The following tables provide normal duty and heavy duty drive ratings
(including continuous, 1 minute, and 3 second).
Table A.A 400V AC Ratings (AC Input/AC Output)
Table A.B 480V AC Ratings (AC Input/AC Output)
Table A.C 600V AC Ratings (AC Input/AC Output)
2
0
4
6
8
360
Output
(Amps)
293 Amps
(80%)
Carrier Frequency (kHz)
Drive
Catalog
Number
Frame
PWM
Freq.
(kHz)
Output Power Output Current (with 400V AC Induction Motor)
(1)
HP (kW)
Cont. 110%
1 min.
150%
3 secs.
Cont. 150%
1 min.
200%
3 secs.
ND HD ND ND ND HD HD HD
20LC360 2 4 268 (200) 200 (150) 360 396 540 264 396 540
20LC650 3A 4 500 (370) 365 (270) 650 715 975 475 715 975
20LC1K2 3B 4 960 (715) 700 (525) 1250 1375 1875 915 1375 1875
(1)
Frame 2 ratings are based on 50 °C ambient and 50 °C coolant.
Frame 3A and 3B ratings are based on 40 °C ambient and 40 °C coolant.
Drive
Catalog
Number
Frame
PWM
Freq.
(kHz)
Output Power Output Current (with 480V AC Induction Motor)
(1)
HP (kW)
Cont. 110%
1 min.
150%
3 secs.
Cont. 150%
1 min.
200%
3 secs.
ND HD ND ND ND HD HD HD
20LD360 2 4 300 (224) 235 (175) 360 396 540 264 396 540
20LD650 3A 4 600 (445) 440 (325) 650 715 975 475 715 975
20LD1K2 3B 4 1150 (860) 845 (630) 1250 1375 1875 915 1375 1875
(1)
Frame 2 ratings are based on 50 °C ambient and 50 °C coolant.
Frame 3A and 3B ratings are based on 40 °C ambient and 40 °C coolant.
Drive
Catalog
Number
Frame
PWM
Freq.
(kHz)
Output Power Output Current (with 600V AC Induction Motor)
(1)
HP (kW)
Cont. 110%
1 min.
150%
3 secs.
Cont. 150%
1 min.
200%
3 secs.
ND HD ND ND ND HD HD HD
20LE425 3A 4 465 (345) 345 (255) 425 470 640 315 470 640
20LE800 3B 4 870 (650) 640 (480) 800 885 1200 590 885 1200
20LE1K1 3B 2
(2)
1275 (955) 935 (695) 1175 1295 1765 860 1295 1765
(1)
Frame 3A and 3B ratings are based on 40 °C ambient and 40 °C coolant.
(2)
Must operate at only 2 kHz PWM, and only as a stand-alone inverter module (“K” in catalog string position 13).