Owner's manual
Troubleshooting 6-3
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P
Table 6.A Status Indications
HIM Indication
The LCD HIM also provides visual notification of a fault or alarm condition.
Item Name Color State Description
➊
POWER Green Steady Illuminates when power is applied to the drive.
➋
STS
(Status)
Green Flashing Drive ready, but not running and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing,
Drive Stopped
A type 2 alarm condition exists, the drive cannot be
started. Check parameter 211 [Drive Alarm 2].
Flashing,
Drive Running
An intermittent type 1 alarm condition is occurring.
Check parameter 211 [Drive Alarm 1].
Steady,
Drive Running
A continuous type 1 alarm condition exists.
Check parameter 211 [Drive Alarm 1].
Red Flashing Fault has occurred. Check [Fault x Code] or Fault Queue.
Steady A non-resettable fault has occurred.
➌
PORT
See the 20-COMM-x
Communication Adapter
User Manual.
Status of DPI port internal communications (if present).
MOD Status of communications module (when installed).
NET A Status of network (if connected).
NET B Status of secondary network (if connected).
Condition Display
Drive is indicating a fault.
The LCD HIM immediately reports the fault condition by
displaying the following information:
• “Faulted” appears in the status line
• Fault number
• Fault name
• Time that has passed since fault occurred
Press Esc to regain HIM control.
Drive is indicating an alarm.
The LCD HIM immediately reports the alarm condition by
displaying the following information:
• Alarm name (Type 2 alarms only)
• Alarm bell graphic
F-> Faulted Auto
0.0 Hz
Main Menu:
Diagnostics
Parameter
— Fault — F 5
OverVoltage
Time Since Fault
0000:23:52
F-> Power Loss Auto
0.0
Hz
Main Menu:
Diagnostics
Parameter
Device Select