Alarm
No.
Type
(1)
(1)
See the PowerFlex 700 Series B User Manual for a description of alarm types.
Description
Dig In
ConflictA
17
Digital input functions are in conflict. Combinations marked with a “ ” will
cause an alarm.
Dig In
ConflictB
18
A digital Start input has been configured without a Stop input or other
functions are in conflict. Combinations that conflict are marked with a “ ” and
will cause an alarm.
Dig In
ConflictC
19
More than one physical input has been configured to the same input function.
Multiple configurations are not allowed for the following input functions:
Forward/Reverse Run Reverse Bus Regulation Mode B
Speed Select 1 Jog Forward Acc2 / Dec2
Speed Select 2 Jog Reverse Accel 2
Speed Select 3 Run Decel 2
Run Forward Stop Mode B
TB Man Ref
Cflct
30
Occurs when:
“Auto/Manual” is selected (default) for Parameter 363 [Digital In3 Sel]
and
Parameter 096 [TB Man Ref Sel] has been reprogrammed.
No other use for the selected analog input may be programmed.
Example: If Parameter 096 [TB Man Ref Sel] is reprogrammed to “2” (Analog
In 2), all of the factory default uses for Analog In 2 must be reprogrammed
(such as Parameters 90, 117, 128 and 179). Refer to the Auto/Manual
Examples section of the PowerFlex 700 Series B User Manual.
To correct:
Verify/reprogram the parameters that reference an analog input
or
Reprogram Parameter 363 [Digital In3 Sel] to another function or “0” (Not
Used).
Acc2/Dec2 Accel 2 Decel 2 Jog 1/2 Jog Fwd Jog Rev Fwd/Rev
Acc2/Dec2
Accel 2
Decel 2
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev
Start Stop-CF Run Run Fwd Run Rev Jog 1/2 Jog Fwd Jog Rev Fwd/Rev
Start
Stop-CF
Run
Run Fwd
Run Rev
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev