Owner's manual

PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009
28
3-Wire Control
Internal supply
No changes required if parameters
are at factory default settings
3-Wire Control
External supply (I/O Board
dependent). Requires 3-wire
functions only ([Digital In1
Sel]). Using 2-wire selections
will cause a type 2 alarm.
No changes required if parameters
are at factory default settings
Digital Input
PLC Output Card (Board
dependent). Resistors are
recommended to dissipate
leakage current.
No changes required if parameters
are at factory default settings
Digital Output
Relays shown in powered
state with drive faulted. See
Table 9
.
Vector Control:
2 relays at terminal 14…16
Standard Control:
1 relay at terminals 14…16
Vector Control:
Select Source to Activate:
Parameters 380/384/388
Standard Control:
Select Source to Activate:
Parameters 380/384
Enable Input Vector Control
Configure with Parameter 366.
For dedicated hardware Enable:
Remove Jumper J10 (see page 30
)
Standard Control:
Configure with Parameter 366
(1)
Refer to the Attention statements on page 24 for important bipolar wiring information.
(2)
A PTC (Positive Temperature Coefficient) device (motor thermistor), embedded in the motor windings, can be
monitored by the drive for motor thermal protection.
(3)
Important: Programming inputs for 2 wire control (Run) deactivates all HIM Start buttons unless Parameter 192
[Save HIM Ref], bit 1 (Manual Mode) = “1.” This will allow the HIM to control Start and Jog.
Input/Output Connection Example Required Parameter Changes
Start
24
25
26
27
28
Stop
Start
25
27
28
Stop
115V
/
+24V
Neutral/
Common
25
27
28
Control from
Prog. Controller
Neutral/
Common
10k Ohm, 2 Watt
Power Source
11
12
13
14
15
16
Fault
NOT Fault
NOT Run
Run
or
32