User Manual

3-20 Programming and Parameters
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Inputs & Outputs File
File
Group
No. Parameter Name & Description Values
INPUTS & OUTPUTS
Mux’ed Temps
330 [IGBT NTC Temp1]
Displays the temperature measured in IGBT module 1.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1°C
331 [IGBT NTC Temp2]
Displays the temperature measured in IGBT module 2.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1°C
332 [IGBT NTC Temp3]
Displays the temperature measured in IGBT module 3.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1°C
333 [IGBT NTC Temp4]
Displays the temperature measured in IGBT module 4.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1°C
334 [Coldplate Temp1]
Displays the temperature measured on the first coldplate.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1°C
335 [IGBT NTC Temp5]
Displays the temperature measured in IGBT module 5.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1°C
336 [IGBT NTC Temp6]
Displays the temperature measured in IGBT module 6.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1°C
337 [IGBT NTC Temp7]
Displays the temperature measured in IGBT module 7.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1°C
338 [IGBT NTC Temp8]
Displays the temperature measured in IGBT module 8.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1°C
339 [Coldplate Temp2]
Displays the temperature measured on the second coldplate.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1°C
Digital Inputs
350 [Dig In Status]
A set of bits displaying the status of the digital input.
Bit 0 (Aux Input) is set when Aux Input is on.
Bit 1 (Sel Switch) is set when the DPI SLAVE/MASTER switch on the Active Converter control PCB assembly (Figure 1.3 on
page 1-5) is in the DPI MASTER position (Stand Alone operation).
351 [Dig In Frc Mask]
A set of bits to select which input bits are forced.
Bit 0 (Aux Input) – Enables forcing of the Aux Input signal. This feature requires a password to operate.
Bit 1 (Sel Switch) – Enables forcing of the DPI SLAVE/MASTER switch signal on the Active Converter control PCB assembly
(Figure 1.3 on page 1-5
). This feature requires a password to operate.
Bit
Definition
Sel Switch
Aux Input
Default xxxxxxxxxxxxxx00
Bit 1514131211109876543210
0 = Disabled
1 = Enabled
x = Reserved
Bit
Definition
Sel Switch
Aux Input
Default xxxxxxxxxxxxxx00
Bit 1514131211109876543210
0 = Disabled
1 = Enabled
x = Reserved
Read Only