Programming and Parameters 3-11
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Dynamic Control File
File
Group
No. Parameter Name & Description Values
DYNAMIC CONTROL
Current Loop
150 [Reduce Ilmt Sel]
Enables the use of a reduced current limit when in overload.
“Disabled” = The Converter current limit is always the value in parameter 100 -
[Active I Lmt].
“Enabled” = The Converter current limit will switch to the value set by parameter
101 - [Active OL I Lmt] when in overload.
Default:
Options:
1
0
1
“Disabled”
“Disabled”
“Enabled”
151 [Active I Cmd]
Displays the commanded active current.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1 Amps
152 [Inductance]
Sets the input filter inductance. When set to non-zero, this value is used to
calculate the tuning coefficients for the current loop CML Ki and Kp.
Default:
Min/Max:
Units:
Rated µH
0/32767 µH
1 µH
153 [CML Bandwidth]
Sets the Current Minor Loop bandwidth. When set to non-zero, this value is
used to calculate the tuning coefficients for the current loop CML Ki and Kp.
Default:
Min/Max:
Units:
1500 Rad/sec
0/4000 Rad/sec
1 Rad/sec
154 [CML Damping]
Sets the Current Minor Loop damping. When set to non-zero, this value is used
to calculate the tuning coefficients for the current loop CML Ki and Kp.
Default:
Min/Max:
Units:
1.6
0.5/5.0
None
155 [CML Ki]
Tunes the integral gain of the current loop.
Default:
Min/Max:
Units:
Drive Size Dependent
0/32767
None
156 [CML Kp]
Tunes the proportional gain of the current loop.
Default:
Min/Max:
Units:
Drive Size Dependent
0/32767
None
157 [PF Bandwidth]
Sets the bandwidth of the current regulator maintaining the desired power factor.
This is used only when parameter 051 - [Option Select] Bit 1 (Unbal V Comp) is
set to "1" to enable unbalanced voltage compensation.
Default:
Min/Max:
Units:
Drive Size Dependent
0/4000
None
158 [Reactive I Lmt]
Displays the calculated reactive current limit.
Default:
Min/Max:
Units:
Read Only
0.0/3000.0
0.1 Amps
159 [Reactive I Cmd]
Displays the commanded reactive current.
Default:
Min/Max:
Units:
Read Only
-3000.0/+3000.0
0.1 Amps
Voltage Loop
160 [Voltage Loop Sel]
Selects the operation of the voltage loop.
“Optimize Ref” = Vdc reference is calculated to minimize switching losses,
based on the measured AC Line voltage and the minimum voltage required by
the Inverter.
“Manual Ref” = The value set by parameter 060 - [DcLink Reference] is used for
Vdc reference.
“Regen Only” = Reserved for future.
“Open Loop” = The Converter outputs a sinusoidal voltage synchronized to the
AC line with an amplitude set by parameter 063 - [Modulation Index]. This
feature requires a password to operate.
Default:
Options:
0
0
1
2
3
“Optimize Ref”
“Optimize Ref”
“Manual Ref”
“Regen Only”
“Open Loop”
161 [DcLink Command]
Displays the commanded DC Link voltage.
Default:
Min/Max:
Units:
Read Only
0.0/1225.0
0.1 Vdc