Programming and Parameters 3-5
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
MONITOR
Power & Time
024 [Life Time kWh]
Displays the lifetime accumulated kWh. This parameter cannot be reset.
Default:
Min/Max:
Units:
Read Only
0.0/429496729.5
0.1 kWh
025 [Elapsed Run Time]
Displays the accumulated amount of time the Converter has been in run. This
parameter can be reset with parameter 200 - [Reset Meters].
Default:
Min/Max:
Units:
Read Only/Reset
0.0000/429496.7295
0.0001 Hr
026 [Life Run Time]
Displays the accumulated amount of time the Converter has been in run. This
parameter cannot be reset.
Default:
Min/Max:
Units:
Read Only
0.0000/429496.7295
0.0001 Hr
027 [Life Power Time]
Displays the accumulated amount of time the Converter has been powered up. This
parameter cannot be reset to zero.
Default:
Min/Max:
Units:
Read Only
0.0000/429496.7295
0.0001 Hr
028 [Life Pwr Cycles]
Displays the accumulated number of times the Converter has been powered up.
This parameter cannot be reset to zero.
Default:
Min/Max:
Units:
Read Only
0/4294967295
None
Temperature
030 [Ambient Temp]
Displays the measured ambient temperature of the Converter.
Default:
Min/Max:
Units:
Read Only
-40.0/+150.0
0.1°C
031 [IGBT Base Temp]
Displays the measured IGBT base temperature.
Default:
Min/Max:
Units:
Read Only
-40.0/+150.0
0.1°C
032 [IGBT Junction Temp]
Displays the calculated IGBT junction temperature.
Default:
Min/Max:
Units:
Read Only
-40.0/+150.0
0.1°C
Frequency
040 [Line Frequency]
Displays the measured line frequency.
Default:
Min/Max:
Units:
Read Only
0.0/90.0
0.1 Hz
041 [Min Line Freq]
Latches and displays the minimum measured line frequency. The minimum is held
for the time set with parameter 43 - [Min Max Persist].
Default:
Min/Max:
Units:
Read Only
0.0/90.0
0.1 Hz
042 [Max Line Freq]
Latches and displays the maximum measured line frequency. The maximum is held
for the time set with parameter 43 - [Min Max Persist].
Default:
Min/Max:
Units:
Read Only
0.0/90.0
0.1 Hz
043 [Min Max Persist]
Sets the persistence time of the minimum and maximum measured line frequency.
A value of zero results in the minimum and maximum never being reset.
Default:
Min/Max:
Units:
10.0 Sec
0.0/60.0 Sec
0.1 Sec
044 [Change Line Freq]
Displays the measured change in line frequency in Hz/sec.
Default:
Min/Max:
Units:
Read Only
0.0/20.0
0.1 Hz/s
File
Group
No. Parameter Name & Description Values