Owner manual

Specifications A-19
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Table A.G 1000A Unit Spare Part Numbers/Descriptions
Figure A.11 1000A Unit Printed Circuit Board Locations (top view)
Item Availability
(1)
Description Rockwell Catalog No. Qty.
1 1000A SCR Set SK-20S-MCO600-22IO1 6
4 Yes Fan Assembly
(2)
SK-D9-FAN2 1
5 1000A MOV Assembly SK-20S-VBKSDK110 1
7 Yes 40A Fuse (Precharge fuses F7…F11)
(3)
SK-20S-F070B040S or
Westcode Type F070B040S or
Ferraz Shawmut Type 6.921CPgRC14.51 40
5
11 Yes 1000A, 700V Fuse (AC fuses F1…F6)
Torque to 25 N•m (221 lb•in).
SK-20S-069UR2S1000B or
Westcode Type 069UR2S1000B or
Ferraz Shawmut Type 6.9URD32TTF1000
6
12 Yes Fuse Monitoring Switch SK-20S-MS3V1-5 6
13 85 °C Thermostat SK-20S-SWT85KSDKRW 1
14 1000A SCR Wire Harness SK-20S-ZY110-1000 1
17 Yes 1000A Snubber Circuit Board SK-20S-PR-GR3-5 1
19 600A and 1000A Cover SK-20S-RW9582300-A 1
22 600A and 1000A Enclosure SK-20S-RWU600-1000 1
23 15 µF, 1000V Capacitor SK-20S-E62K85153D1W 2
26 4.7K Ohm, 130W Resistor SK-20S-RW36FST4K7K 2
27 4.7 Ohm, 45W Resistor SK-20S-RW33FST4R7K 1
28 1000A Bus Bar Set SK-20S-BBKSDK110 1
31 Terminal Block Assembly SK-20S-TBKSDKRW 1
32 40 mm tall x 40 mm O.D. Insulator
with M10 Thread
SK-20S-IN551520 5
34 Yes Gate Driver Circuit Board
(4)(5)
SK-D9-SCRGDB1 1
35 Yes 480V SCR Precharge Circuit Board
(4)(6)
SK-D9-SCRPRE1-D 1
36 Yes 690V SCR Precharge Circuit Board
(4)(6)
SK-D9-SCRPRE1-F 1
37 Yes Master/Slave or Slave/Slave Wire Harness
(7)
SK-20S-D9-CBL1-DF 1
38 Yes Precharge Relay SK-20S-CA2KN31F7 1
(1)
Important: SCR Bus Supplies are designed to be field maintained only. Normal maintenance components (fan, fuses, fuse monitor
switch, printed circuit boards (precharge, gate, and snubber), and precharge relay are available. Additional catalog numbers are
provided for troubleshooting and technical support information only.
(2)
Extensive disassembly is required to replace the fan assembly. Please consider using Rockwell Automation Remanufacturing Services.
(3)
When replacing these fuses, always properly position them so that their fuse trip indicators (plungers) point toward the fuse trip
detection board.
(4)
This is an ESD sensitive component.
(5)
Not required for 1000A Standalone unit, but required for 1000A Master unit or 1000A Slave unit (both mounted in lower location).
(6)
Not required for 1000A Slave unit, but required for 1000A Standalone unit (mounted in lower location) or 1000A Master unit (mounted in
upper location).
(7)
Not required for a 1000A Standalone unit, but required to connect an existing 1000A Master or Slave unit to another 1000A Slave unit
(gate driver circuit board mounted in lower location).
Precharge Board
SK-D9-SCRPRE1-x
Gate Drive Board
SK-D9-SCRGDB1
1000A
Slave Unit
1000A
Master Unit
1000A
Standalone Unit
Gate Driver Board
SK-D9-SCRGDB1
Precharge Board
SK-D9-SCRPRE1-x