A-10 Specifications
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
Table A.D 690V, 50Hz Line Reactor Selection
Drives Ranges of Drives DC Amp Sum for Typical Supply Transformers
(1)
Line Reactor
Sum of
DC Amps
630 kVA
5%
123
µH
800 kVA
5%
95
µH
1000 kVA
5.5%
86
µH
1250 kVA
6%
75
µH
1600 kVA
6%
59
µH
2500 kVA
6.5%
42
µH
3000 kVA
6.5%
33
µH
Induct.
[µH]
Catalog No.
1321-
(2)
up to 203
130-150 130-157 130-162 130-170 140-180 150-185 2x150 3R160-B
(3)
130-175 151-190 158-203 163-203 171--203 181-203 186-203 230 3R160-C
176-203 191-203 150 3R160-B
75 3R160-A
204 to 255
204-210 204-220 2x110 3R200-B
(3)
204-206 204-230 204-245 204-255 204-255 211-255 221-255 185 3R200-C
207-255 231-255 246-255 110 3R200-B
55 3R200-A
256 to 319
256-260 2x90 3RB250-B
(3)
256-260 256-270 256-290 256-319 256-319 261-319 150 3RB250-C
256-280 261-319 271-319 291-319 90 3RB250-B
281-319 45 3RB250-A
320 to 407
320-360 320-407 320-407 125 3RB320-C
320-360 320-380 320-407 361-407 75 3RB320-B
320-407 361-407 381-407 40 3RB320-A
408 to 509
408-465 408-509 105 3RB400-C
408-414 408-450 408-509 466-509 60 3RB400-B
408-500 415-509 451-509 30 3RB400-A
510 to 635
510-520 510-580 85 3R500-C
510-538 510-570 521-635 581-635 50 3R500-B
510-540 539-635 571-635 25 3R500-A
636 to 763
636-650 65 3R600-C
636-763 651-763 40 3R600-B
661-763 20 3R600-A
764 to 938
764-780 48 3R750-C
764-850 781-938 29 3R750-B
851-938 15 3R750-A
939 to 1K0
42 3R850-C
939-1K0 939-1K0 27 3R850-B
15 3R850-A
(1)
The inductance value of the supply transformers includes 2.5 µH for 10 m feeder cable.
(2)
The number in the catalog string represents the fundamental AC current of the reactor.
(3)
Connect two reactors in series.