Owner manual
1-20 Installation/Wiring
PowerFlex SCR Bus Supply User Manual
Publication 20S-UM001G-EN-P
• Conformity of the drive with CE EMC requirements does not guarantee
an entire machine installation complies with CE EMC requirements.
Many factors can influence total machine/installation compliance.
Essential Requirements for CE Compliance
Conditions 1…5 listed below must be satisfied for the PowerFlex SCR Bus
Supply to meet the requirements of EN61800-3.
1. Bus Supply and inverter must be PowerFlex type and CE compatible.
2. Externally mounted Line Reactor and HF filter (specified in
Appendix
A) must be connected to the line input as shown in
Figure 1.8 on page 1-12
.
3. Review important precaution/attention statements throughout this
document before installing the drive(s).
4. Grounding as described in General Grounding Requirements
on
page 1-5.
5. Control wiring and DC bus wiring leaving the cabinet must be braided,
shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.
For additional conditions, refer to the respective drive Reference Manual.