PowerFlex 755 IP00, NEMA/UL Open Type Drive
Cable Routing
Control Pod Cable Routing
Supports, clips, and cable ties are provided to help route and secure cabling inside
the Control Pod.
Figure 20 - Frame 8 Control POD Detail
IMPORTANT
• When routing cabling into the control Pod, do not block the cooling fan
outlet.
• Do not ground shield wires to inner sheet metal bucket supporting option
modules.
No. Description
➊ I/O signal cable shield termination points. Use M4 screws and ring terminals provided to tie together and
terminate drain wires and shields.
➋ Ground shield wires to outer sheet metal bucket. Strip cable insulation 25 mm (1 in.) to expose braid. Attach cable
ties around shield and through slots. Pull tight.
➌ Attachment points for cable management devices provided (6 places).
➍ Cable support ladder.
➎ Fan outlet. Keep clear to help ensure proper cooling.
➏ Control cable entry and routing.
➐ Human Interface Module (HIM) cable entry and routing.
➑ Shield termination points.
➒ Inverter Fiber-optic connection
➓ Internal 24V power connection