Installation Instructions Owner's manual

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013 51
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Table 21 - 810 Volt DC Input Frames 1…6 Drive Protection Devices
Table 22 - 932Volt DC Input Frames 5 & 6 Drive Protection Devices
20DJ180
(1)
6 150 198 400 HSJ400
125 171.2 400 HSJ400
20DJ248
(1)
6 200 272 400 HSJ400
150 198 400 HSJ400
(1) Also applies to “R” voltage class. s must be applied in the (+) leg and (-) leg of the DC Common Bus.
(2) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.
Drive Cat. No. Frame HP Rating DC Input Ratings Fuse Non-Time Delay
(1)
(1) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.
ND HD Amps
20DE1P7 1 1 0.75 1.5 3 JKS-3
20DE2P7 1 2 1.5 2.4 6 JKS-6
20DE3P9 1 3 2 3.5 6 JKS-6
20DE6P1 1 5 3 6.2 10 JKS-10
20DE9P0 1 7.5 5 9.1 15 HSJ15
20DE011 1 10 7.5 11.5 20 HSJ20
20DE017 1 15 10 18 30 HSJ30
20DE022 2 20 15 23.6 40 HSJ40
20DE027 2 25 20 29 50 HSJ50
20DE032 3 30 25 34.3 60 HSJ60
20DE041 3 40 30 43.9 70 HSJ70
20DE052 3 50 40 55.7 90 HSJ90
20DE062 4 60 50 68.0 125 HSJ125
20DT099 5 100 108.6 150 HSJ150
75 84.5 150 HSJ150
20DT144 6 150 158 200 HSJ200
125 137.1 200 HSJ200
Drive Cat. No. Frame kW Rating DC Input Ratings Fuse Non-Time Delay
(1)
(1) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.
ND HD Amps
20DW098 5 90 92.3 160 HSJ160
75 92.3 160 HSJ160
20DW142 6 132 162.2 250 HSJ250
110 134.9 250 HSJ250
Drive Cat. No. Frame HP Rating DC Input Ratings Fuse Non-Time Delay
(2)
ND HD Amps