Installation Instructions Owner's manual
Rockwell Automation Publication 20D-IN024C-EN-P - July 2013 49
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Table 17 - 690 Volt AC Input Frames 5 & 6 Drive Protection Devices
Table 18 - 325 Volt DC Input Frames 1…6 Drive Protection Devices
Drive
Cat. No.
Frame
kW Rating Input Ratings Dual Element Time Delay
Fuse
Non-Time Delay Fuse Circuit Breaker
(3)
Motor Circuit Protector
(5)
ND HD Amps kVA Min
(1)
Max
(2)
Min
(2)
Max
(3)
Max
(4)
Max
(5)
20DF052 5 45 – 46.9 59.5 60 110 60 175 175 –
– 37.5 40.1 48.0 50 90 50 150 150 –
20DF060 5 55 – 57.7 68.9 80 125 80 225 225 –
– 45 46.9 59.5 60 110 60 175 175 –
20DF082 5 75 – 79.0 94.4 100 200 100 375 375 –
– 55 57.7 68.9 80 125 80 225 225 –
20DF098 5 90 – 94.7 113 125 200 125 375 375 –
– 75 79.0 94.4 100 200 100 375 375 –
20DF119 6 110 – 115 138 150 250 150 400 – –
– 90 92.9 113 125 200 125 375 – –
20DF142 6 132 – 139 165.9 175 300 175 450 – –
– 110 115 137 150 250 150 400 – –
(1) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
Drive Cat. No. Frame HP Rating DC Input Ratings Fuse Non-Time Delay
(3)
(3) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Ferraz Shawmut Type HSJ, all sizes. For any other devices, please contact the factory.
ND HD Amps
20DB015 1 5 3 16 30 HSJ30
20DB022 1 7.5 5 23.3 45 HSJ45
20DB028 2 10 7.5 30 60 HSJ60
20DB042 3 15 10 45 90 HSJ90
20DB052 3 20 15 55 100 HSJ100
20DB070 4 25 20 75.3 150 HSJ150
20DB080 4 30 25 85.8 175 HSJ175
20DN104
(1)
(1) Catalog number corresponds to output amps for these drives. Drive must be programmed to lower voltage to obtain higher currents
shown at right.
5 40 30 114.1 225 HSJ225
20DN130
(1)
5 50 40 142.6 250 HSJ250
20DN154
(1)
6 60 50 169 300 HSJ300
20DN192
(1)
6 75 60 210.6 400 HSJ400
20DN260
(1)(2)
(2) Catalog number corresponds to drives with precharge only.
6 100 75 272.1 400 HSJ400