Installation Instructions Owner's manual

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013 47
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Table 15 - 480 Volt AC Input Frames 1…6 Drive Protection Devices
20DC085
(1)
4 45 81.4 56.4 110 200 110 300 300 150
37 68.9 47.8 90 175 90 275 300 100
20DC105 5 55 100.5 69.6 125 225 125 400 300 150
45 81.4 56.4 110 175 110 300 300 150
20DC125 5 55 121.1 83.9 150 275 150 500 375 250
45 101 63.7 125 200 125 375 375 150
20DC140 5 75 135.6 94 200 300 200 400 400 250
55 121 69.6 150 225 150 300 300 150
20DC170 6 90 164.6 114 250 375 250 600 500 250
75 136 94 200 300 200 550 400 250
20DC205
(2)
6 110 198.5 138 250 450 250 600 600 400
90 164 114 250 375 250 600 500 250
20DC260 6 132 254.7 166 350 550 350 750 750 400
110 199 138 250 450 250 600 600 400
(1) 20DC085 current rating is limited to 45 degrees C ambient.
(2) 20DC205 current rating is limited to 40 degrees C ambient.
(3) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(5) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(6) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(7) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(8) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(9) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground
systems.
(10) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings
.
(11) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal
considerations may require a larger enclosure.
Drive Cat.
No.
Frame
kW Rating Input
Ratings
Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(5)
Motor
Circuit
Protector
(7)
140M Motor Starter with Adjustable Current Range
(8)(9)
ND HD Amps kVA Min
(3)
Max
(4)
Min
(5)
Max
(6)
Max
(6)
Max
(8)
Available Cat. No.s
(10)
Minimum Enclosure
Volume (in.
3
)
(11)
Drive Cat.
No.
Frame
HP Rating Input Ratings Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
140M Motor Starter with Adjustable Current Range
(6)(7)
ND HD Amps kVA Min
(1)
Max
(2)
Min
(3)
Max
(4)
Max
(4)
Max
(6)
Available Cat. No.s
(8)
Minimum Enclosure
Volume (in.
3
)
(9)
20DD2P1 1 1 0.7
5
1.6 1.4 3 6 3 8 15 3 M-C2E-B25 7269
20DD3P4 1 2 1.5 2.6 2.2 4 8 4 12 15 7 M-C2E-B40 M-D8E-B40 7269
20DD5P0 1 3 2 3.9 3.2 6 10 6 20 20 7 M-C2E-B63 M-D8E-B63 7269
20DD8P0 1 5 3 6.9 5.7 10 15 10 30 30 15 M-C2E-C10 M-D8E-C10 M-F8E-C10 7269
20DD011 1 7.5 5 9.5 7.9 15 20 15 40 40 15 M-C2E-C16 M-D8E-C16 M-F8E-C16 7269
20DD014 1 10 7.5 12.5 10.4 17.5 30 17.5 50 50 20 M-C2E-C16 M-D8E-C16 M-F8E-C16 7269
20DD022 1 15 10 19.9 16.6 25 50 25 80 80 30 M-D8E-C25 M-F8E-C25 7269
20DD027 2 20 15 24.8 20.6 35 60 35 100 100 50 M-F8E-C32 7269
20DD034 2 25 20 31.2 25.9 40 70 40 125 125 50 M-F8E-C45 7269
20DD040 3 30 25 36.7 30.5 50 90 50 150 150 50 M-F8E-C45 13630
20DD052 3 40 30 47.7 39.7 60 110 60 200 200 70
20DD065 3 50 40 59.6 49.6 80 125 80 250 250 100
20DD077 4 60 72.3 60.1 100 170 100 300 300 100
50 59.6 49.6 80 125 80 250 250 100
20DD096 5 75 90.1 74.9 125 200 125 350 350 125
60 72.3 60.1 100 170 100 300 300 100