Owner's manual

Installation/Wiring 1-17
6 Wire Common
Mode
Capacitors
Remove the wire guard from the Power Terminal
Block. Disconnect the three green/yellow wires from
the two “PE” terminals shown in Figure 1.4
. Insulate
and secure the wires to guard against unintentional
contact with chassis or components.
Please
refer to
Power
Terminal
Blocks,
Frame 6
on page
1-12
.
MOV’s
Input Filter
Capacitors
!
ATTENTION: The disconnecting MOV must be used on a
grounded system.
Frames Jumper Component Jumper Location No.