Owner's manual
A-12 Supplemental Information
480 Volt AC Input Frames 9…11 Drive Protection Devices
600 Volt AC Input Frames 1…6 Drive Protection Devices
Drive Catalog
Number
Frame
HP Rating Input
Ratings
Dual Element Time Delay Fuse Non-Time Delay Fuse Bussmann Style Semi-
Conductor Fuse
Circuit
Breaker
(3)
Motor Circuit
Protector
(5)
ND HD Amps Min.
(1)
Max.
(2)
Min.
(1)
Max.
(3)
Max.
(4)
Max.
(5)
20DD261 9 200 - 252 350 550 350 700 170M5813 700 400
- 150 207 275 450 275 600 170M5813 600 300
20DD300 9 250 - 290 400 650 400 900 170M5813 900 400
- 200 247 350 550 350 700 170M5813 700 400
20DD385 10 300 - 372 500 850 500 1100 170M5813 1100 600
- 250 302 400 650 400 900 170M5813 900 400
20DD460 10 350 - 444 600 1000 600 1300 170M8547 1300 600
- 300 388 500 850 500 1100 170M8547 1100 600
20DD500 10 450 - 483 650 1000 650 1500 170M8547 1500 700
- 350 423 550 900 550 1200 170M8547 1200 600
20DD590 11 500 - 570 750
(1 per phs)
375 (2 per phs)
1300 750 (1 per phs)
375 (2 per phs)
1700 170M5813 1700 800
- 450 524 700
(1 per phs)
350 (2 per phs)
1100 700 (1 per phs)
350 (2 per phs)
1500 170M5813 1500 700
20DD650 11 500 - 628 800 (1 per phs)
400 (2 per phs)
1400 800 (1 per phs)
400 (2 per phs)
1900 170M5813 1900 800
- 500 594 750 (1 per phs)
375 (2 per phs)
1300 750 (1 per phs)
375 (2 per phs)
1700 170M5813 1700 800
20DD730 11 600 - 705 900
(1 per phs)
450 (2 per phs)
1600 900 (1 per phs)
450 (2 per phs)
2100 170M5813 2100 900
- 500 655 850 (1 per phs)
425 (2 per phs)
1400 850
(1 per phs)
425 (2 per phs)
1900 170M5813 1900 900
(1) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
Drive
Catalog
Number
Frame
HP Rating Input Ratings Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
140M Motor Starter with Adjustable Current Range
(6)(7)
ND HD Amps kVA Min.
(1)
Max.
(2)
Min.
(3)
Max.
(4)
Max.
(4)
Max.
(6)
Available Catalog Numbers
(8)
Minimum Enclosure
Volume (in.
3
)
(9)
20DE1P7 1 1 0.75 1.3 1.4 2 4 2 6 15 3 M-C2E-B16 – – 7269
20DE2P7 1 2 1.5 2.1 2.1 3 6 3 10 15 3 M-C2E-B25 – – 7269
20DE3P9 1 3 2 3.0 3.1 6 9 6 15 15 7 M-C2E-B40 M-D8E-B40 – 7269
20DE6P1 1 5 3 5.3 5.5 9 12 9 20 20 15 – M-D8E-B63 – 7269
20DE9P0 1 7.5 5 7.8 8.1 10 20 10 35 30 15 – M-D8E-C10 M-F8E-C10 7269
20DE011 1 10 7.5 9.9 10.2 15 25 15 40 40 15 – M-D8E-C10 M-F8E-C10 7269
20DE017 1 15 10 15.4 16.0 20 40 20 60 50 20 – M-D8E-C16 M-F8E-C16 7269
20DE022 2 20 15 20.2 21.0 30 50 30 80 80 30 – – M-F8E-C25 7269
20DE027 2 25 20 24.8 25.7 35 60 35 100 100 50 – – M-F8E-C25 7269
20DE032 3 30 25 29.4 30.5 40 70 40 125 125 50 – – M-F8E-C32 13630
20DE041 3 40 30 37.6 39.1 50 90 50 150 150 100 – – – –
20DE052 3 50 40 47.7 49.6 60 110 60 200 200 100 – – – –
20DE062 4 60 50 58.2 60.5 80 125 80 225 225 100 – – – –
20DE077 5 75 – 72.3 75.1 90 150 90 300 300 100 – – – –
– 60 58.2 60.5 90 125 90 250 250 100 – – – –