Owner's manual
Supplemental Information A-11
480 Volt AC Input Frames 1…6 Drive Protection Devices
20DC650 11 355 - 655 850 (1 per phs)
425 (2 per phs)
1400 850 (1 per phs)
425 (2 per phs)
1900 170M5813 1900 1000
- 315 594 750 (1 per phs)
375 (2 per phs)
1300 750 (1 per phs)
375 (2 per phs)
1700 170M5813 1700 800
20DC730 11 400 - 735 1000 (1 per phs)
500 (2 per phs)
1600 1000 (1 per phs)
500 (2 per phs)
2100 170M5813 2100 1200
- 355 655 850 (1 per phs)
425 (2 per phs)
1400 850 (1 per phs)
425 (2 per phs)
1900 170M5813 1900 1000
(1) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
Drive Catalog
Number
Frame
kW Rating Input
Ratings
Dual Element Time Delay Fuse Non-Time Delay Fuse Bussmann Style Semi-
Conductor Fuse
Circuit
Breaker
(3)
Motor Circuit
Protector
(5)
ND HD Amps Min.
(1)
Max.
(2)
Min.
(1)
Max.
(3)
Max.
(4)
Max.
(5)
Drive
Catalog
Number
Frame
HP Rating Input Ratings Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
140M Motor Starter with Adjustable Current Range
(6)(7)
ND HD Amps kVA Min.
(1)
Max.
(2)
Min.
(3)
Max.
(4
)
Max.
(4)
Max.
(6)
Available Catalog Numbers
(8)
Minimum Enclosure
Volume (in.
3
)
(9)
20DD2P1 1 1 0.7
5
1.6 1.4 3 6 3 8 15 3 M-C2E-B25 – – 7269
20DD3P4 1 2 1.5 2.6 2.2 4 8 4 12 15 7 M-C2E-B40 M-D8E-B40 – 7269
20DD5P0 1 3 2 3.9 3.2 6 10 6 20 20 7 M-C2E-B63 M-D8E-B63 – 7269
20DD8P0 1 5 3 6.9 5.7 10 15 10 30 30 15 M-C2E-C10 M-D8E-C10 M-F8E-C10 7269
20DD011 1 7.5 5 9.5 7.9 15 20 15 40 40 15 M-C2E-C16 M-D8E-C16 M-F8E-C16 7269
20DD014 1 10 7.5 12.5 10.4 17.5 30 17.5 50 50 20 M-C2E-C16 M-D8E-C16 M-F8E-C16 7269
20DD022 1 15 10 19.9 16.6 25 50 25 80 80 30 – M-D8E-C25 M-F8E-C25 7269
20DD027 2 20 15 24.8 20.6 35 60 35 100 100 50 – – M-F8E-C32 7269
20DD034 2 25 20 31.2 25.9 40 70 40 125 125 50 – – M-F8E-C45 7269
20DD040 3 30 25 36.7 30.5 50 90 50 150 150 50 – – M-F8E-C45 13630
20DD052 3 40 30 47.7 39.7 60 110 60 200 200 70 – – – –
20DD065 3 50 40 59.6 49.6 80 125 80 250 250 100 – – – –
20DD077 4 60 – 72.3 60.1 100 170 100 300 300 100 – – – –
– 50 59.6 49.6 80 125 80 250 250 100 – – – –
20DD096 5 75 – 90.1 74.9 125 200 125 350 350 125 – – – –
– 60 72.3 60.1 100 170 100 300 300 100 – – – –
20DD125 5 100 – 117 97.6 150 250 150 500 375 150 – – – –
– 75 90.1 74.9 125 200 125 350 350 125 – – – –
20DD156 6 125 – 146.5 121.7 200 350 200 600 450 250 – – – –
– 100 131 97.6 175 250 175 500 375 250 – – – –
20DD180 6 150 – 169 140.5 225 400 225 600 500 250 – – – –
– 125 147 121.7 200 350 200 600 450 250 – – – –
20DD248 6 200 232.8 188 300 550 300 700 700 400 – – – –
150 169 140.5 225 400 225 600 500 250 – – – –
(1) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(6) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(8) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings
.
(9) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger
enclosure.