A-2 Supplemental Information
Agency
Certification
The drive is designed to meet applicable requirements of the
following codes/standards:
IEC 61800-2 Adjustable speed electrical power drive systems -
General requirements
IEC 61800-5-1 Adjustable speed electrical power drive systems
- Safety requirements
NFPA 70 – US National Electric Code
NEMA 250 – Enclosures for Electrical Equipment
The drive is designed to meet applicable requirements of the
following codes/standards:
IEC 61800-2 Adjustable speed electrical power drive systems -
General requirements
IEC 61800-5-1 Adjustable speed electrical power drive systems
- Safety requirements
NFPA 70 - US National Electrical Code
UL and cUL Listed to UL508C and CAN/CSA - 22.2 No. 14-95 UL and cUL Listed to UL508C and CAN/CSA - 22.2 No. 14-95
Marked for all applicable European Directives
EMC Directive (89/336/EEC)
Emissions
EN 61800-3 Adjustable Speed electrical power drive
systems Part 3
Immunity
EN 61800-3 Second Environment, Restricted Distribution
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power
Installations
Marked for all applicable European Directives
EMC Directive (89/336/EEC)
Emissions
EN 61800-3 Adjustable Speed electrical power drive
systems Part 3
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power
Installations
TUV Rheinland (applies to frames 1 - 6, 200/400V, and frames 5
& 6, 690V only)
TUV Functional Safety Report only for frames 1 - 4, 600V (no FS
mark on the label)
TUV functional safety report only (no FS mark on the label)
Environment Altitude: 1000 m (3300 ft.) max. without derating 1000 m (3300 ft) max. without derating
Surrounding Air Temperature
without Derating:
Based on drive rating, refer to Drive Frame chapters
Open Type: 0 to 50° C (32 to 122° F)
IP20: 0 to 50° C (32 to 122° F)
NEMA Type 1: 0 to 40° C (32 to 104 ° F)
IP56, NEMA Type 4X: 0 to 40 ° C (32 to 104 ° F)
Note: Frames 9 & 10 are rated 0 to 40 ° C (32 to 104 ° F)
surrounding air.
Storage Temperature (all
const.):
-40 to 70° C (-40 to 158° F) –40 to 70 degrees C (–40 to 158 degrees F)
Relative Humidity: 5 to 95% non-condensing 5 to 95% non-condensing
Shock: 10G peak for 11 ms duration (+/- 1.0 ms) 15G peak for 11ms duration (±1.0 ms)
Vibration: 0.152 mm (0.006 in.) displacement, 1G peak, 5.5 Hz 2 mm (0.0787 in.) displacement, 1G peak
EN50178 / EN60068-2-6
Atmosphere Important: Drive must
not be installed in an area where the
ambient atmosphere contains volatile or corrosive gas, vapors
or dust. If the drive is not going to be installed for a period of
time, it must be stored in an area where it will not be exposed to
a corrosive atmosphere.
Electrical AC Input
Voltage Tolerance: See Input Voltage Range/Tolerance
on page C-1 for Full Power
and Operating Range
Frequency Tolerance: 47-63 Hz 47-63 Hz.
Input Phases: Three-phase input provides full rating for all drives. Single-phase
operation provides 50% of rated current.
Three-phase input provides full rating for all drives.
Single-phase operation provides 50% of rated current.
DC Input
Voltage Tolerance +/- 10% of Nominal Bus Voltage (above)
Displacement Power Factor: 0.98 across speed range 0.98 across speed range
Efficiency: 97.5% at rated amps, nominal line volts. 97.5% at rated amps, nominal line volts.
Max. Short Circuit Current
Rating:
Using Recommended Fuse
or Circuit Breaker Type
Maximum short circuit current rating to match specified fuse/
circuit breaker capability.
200,000 Amps
200,000 Amps
Maximum Drive to Motor Power
Ratio
The drive to motor rating cannot exceed a 2:1 ratio The drive to motor rating cannot exceed a 2:1 ratio
Category Specification
Frames 1-6 (690V Drive frames 5 & 6 only) Frames 9 & up
U
L
USC
®
TUV
Rheinland
Product Safety
.
.
Production inspected
W
E
C
TUV
Rheinland
..
Functional
Safety
Bauart geprüft
Type approved
EN 50178