Category Specification
Frames 1-6 (690V Drive frames 5 & 6 only) Frames 9 & up
Protection 200-208V
Drive
240V
Drive
380/400V
Drive
480V
Drive
600V
Drive
690V
Drive
380/400V
Drive
480V
Drive 500V Drive
600V
Drive
690V
Drive
AC Input Overvoltage Trip: 247VAC 285VAC 475VAC 570VAC 690VAC 863VAC 475VAC 570V AC 611V AC 690VAC 863VAC
Bus Overvoltage Trip: 350VDC 405VDC 675VDC 810VDC 1013VDC 1164VDC 675VDC 810VDC 810V DC 1013VDC 1164VDC
Bus Undervoltage Trip: Adjustable Adjustable
Nominal Bus Voltage: 281VDC 324VDC 540VDC 648VDC 810VDC 931VDC 540V DC 648V DC 645VDC 810VDC 931VDC
Heat Sink Thermistor: Monitored by microprocessor overtemp trip Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Current Limit:
Hardware Current Limit:
Instantaneous Current Limit:
Calculated value, 105% of motor rated to 200% of drive rated
105% of 3 sec. rating (158%-210%)
143% of 3 sec rating (215%-287%)
Calculated value, 105% of motor rated to 200% of drive rated
360% of rated Heavy Duty current (typical)
—
Line Transients: Up to 6000 volts peak per IEEE C62.41-1991 up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise Immunity: Showering arc transients up to 1500V peak Showering arc transients up to 1500V peak
Power Ride-Thru: 15 milliseconds at full load 15 milliseconds at full load
Logic Control Ride-Thru 0.25 sec., drive not running 0.25 seconds, drive not running
Ground Fault Trip: Phase-to-ground on drive output Phase-to-ground on drive output