Owner's manual

3-58 Programming and Parameters
No.
Name
Description Values
Linkable
Read-Write
Data Type
503 Current Reg BW
Sets the bandwidth for the current regulator. Par 402 [PWM Frequency] limits the
maximum value. Reducing the value reduces current regulator over-shoot.
Units:
Default:
Min/Max:
R/S
600
100/30000
16-bit
Integer
504 PM AbsEncd Offst
Determined by the autotune procedure.
Default:
Min/Max:
0
0/65535
16-bit
Integer
505 PM TestWait Time
Defines the time interval used for the automated measurement of Par 504 [PM AbsEncd
Offst] for a Permanent Magnet (PM) motor.
Units:
Default:
Min/Max:
mSec
2000
500/5000
16-bit
Integer
506 PM Test Idc Ramp
Defines the ramp rate of the flux producing (d-axis) current reference that is used for the
automated measurement of Par 504 [PM AbsEncd Offst] for a Permanent Magnet (PM)
motor.
Units:
Default:
Min/Max:
Comm Scale:
%/mS
0.1
0.0/195.3
x 10
16-bit
Integer
507 PM Test FreqRamp
Defines the ramp rate of the frequency reference that is used for the automated
measurement of Par 504 [PM AbsEncd Offst] for a Permanent Magnet (PM) motor.
Units:
Default:
Min/Max:
Comm Scale:
%/mS
0.1
0.0/195.3
x 10
16-bit
Integer
508 PM Test Freq Ref
Defines the frequency reference that is used for the automated measurement of Par 504
[PM AbsEncd Offst] for a Permanent Magnet (PM) motor.
Units:
Default:
Min/Max:
Comm Scale:
%
10.0
-/+799.9
x 10
16-bit
Integer
509 PM Test I Ref
Defines the amplitude of the flux producing (d-axis) current reference that is used for the
automated measurement of Par 504 [PM AbsEncd Offst] for a Permanent Magnet (PM)
motor.
Units:
Default:
Min/Max:
Comm Scale:
%
30.0
0.0/799.9
x 10
16-bit
Integer
510 FOC Mode Config
Configures Field Oriented Control (FOC) operation.
Note: Bit 15 [LwSpdRflctWv] was added for firmware version 2.06
511 FOC2 Mode Config
Configures Field Oriented Control - 2 (FOC2) operation.
!
ATTENTI ON: Do not modify this parameter.
Motor/Drive instabilities and damage could
result.
Options
Reserved
Reserved
Reserved
Reserved
Reserved
FS PresetSpd
Reserved
Reserved
SrLssFStrtEn
SrLss RdThru
SrLssWeLimit
SrLss WeHold
Reserved
Reserved
Reserved
Reserved
LwSpdRflctWv
Slip Reg En
SlipGain Est
RsEst Update
RsEst Ratio
RsEst Adapt
ReflWaveComp
BusGain Comp
LwSpd VqsReg
Flux Reg Use
Flux Reg En
Reserved
Reserved
Reserved
Reserved
Reserved
Default00000000000000000111001101100000
Bit 313029282726252423222120191817161514131211109 8 7 6 5 4 3 2 1 0
0 = False
1 = True
Bit Definition
23 Enables Sensorless Flying start
26 Sensorless Flying start function will use the speed set in Par 451 [SrLss Preset Spd].
!
ATTENTI ON: Do not modify this parameter.
Motor/Drive instabilities and damage could
result.
Options
LinrSnsr Dir
LnrSnsr Use
Reserved
FlxRatRf Use
NTC Active
Reserved
Reserved
CEMF We Use
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
ReflWaveComp
BusGain Comp
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Default000000000000000001100011001100000
Bit 313029282726252423222120191817161514131211109 8 7 6 5 4 3 2 1 0
0 = False
1 = True