Programming and Parameters 3-51
387 Lgx Timeout Cnfg
Enter a value to configure the drive's response to a Controller to Drive connection
timeout, as detected by the drive.
0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the
appropriate fault bit, in response this event
4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the
appropriate fault bit, in response this event
Default:
Options:
2
0
1
2
3
4
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
388 Lgx Closed Cnfg
Enter a value to configure the drive's response to the controller closing the Controller to
Drive connection.
0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the
appropriate fault bit, in response this event
4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the
appropriate fault bit, in response this event
Default:
Options:
2
0
1
2
3
4
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
389 Lgx LinkChngCnfg
Enter a value to configure the drive's response to Controller to Drive default links being
removed. A default link is a link automatically set up when a communication format is
selected for the Controller to Drive connection.
0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the
appropriate fault bit, in response this event
4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the
appropriate fault bit, in response this event
Default:
Options:
2
0
1
2
3
4
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
No.
Name
Description Values
Linkable
Read-Write
Data Type
!
ATTENTI ON: Risk of injury or equipment damage exists. Parameter 387 [Lgx Timeout Cnfg] lets you determine the
action of the drive if communications are disrupted. By default this parameter causes the drive to fault and coast to a stop.
You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this
parameter does not create hazards of injury or equipment damage.
!
ATTENTI ON: Risk of injury or equipment damage exists. Parameter 388 [Lgx Closed Cnfg] lets you determine the action
of the drive if communications are disrupted. By default this parameter causes the drive to fault and coast to a stop. You can
set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter
does not create hazards of injury or equipment damage.
!
ATTENTION: Risk of injury or equipment damage exists. Parameter 389 [Lgx LinkChngCnfg] lets you determine the
action of the drive if communications are disrupted. By default this parameter causes the drive to fault and coast to a stop.
You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this
parameter does not create hazards of injury or equipment damage.