Programming and Parameters 3-49
375 Inv OT Pend Cnfg
Enter a value to configure the drive's response to a Inverter Over-Temperature (OT)
Pending exception event. This event is triggered when the Inverter NTC (Temperature
protection) function detects the heat-sink temperature reaches to the overload warning
level.
0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the
appropriate fault bit, in response this event
4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the
appropriate fault bit, in response this event
Default:
Options:
1
0
1
2
3
4
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
376 Inv OL Pend Cnfg
Enter a value to configure the drive's response to an Inverter Overload (OL) Pending
exception event. This event is triggered when one of the Inverter Protection
Current-Over-Time functions (Open Loop or Closed Loop) detects current and
temperature at warning levels.
0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the
appropriate fault bit, in response this event
4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the
appropriate fault bit, in response this event
Default:
Options:
1
0
1
2
3
4
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
377 Inv OL Trip Cnfg
Enter a value to configure the drive's response to an Inverter Overload (OL) Trip
exception event. This event is triggered when one of the Inverter Protection
Current-Over-Time functions (Open Loop or Closed Loop) detects current and
temperature at a fault level.
0 “Ignore” Configures the drive to continue running, as normal, when this event occurs
1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
Default:
Options:
1
0
1
2
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
378 Interp Flt Cnfg
Enter a value to configure the drive's response when a Synchronization input to the
Interpolator has been lost or has become excessively irregular.
0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the
appropriate fault bit, in response this event
4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the
appropriate fault bit, in response this event
Default:
Options:
2
0
1
2
3
4
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
379 Ext Flt/Alm Cnfg
Enter a value to configure the drive's response to an External Input exception event. The
event is triggered by a digital input that is configured for auxiliary fault or auxiliary aux
fault by choosing option 11 “Aux Fault” or 12 “AuxFault Inv” in Pars 838 [DigIn 1 Sel], 839
[DigIn 2 Sel], or 840 [DigIn 3 Sel].
0 “Ignore” - Configures the drive to continue running, as normal, when this event
occurs
1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
3 “Flt RampStop” - Configures the drive to perform a ramp stop and set the
appropriate fault bit, in response this event
4 “FltCurLimStp” - Configures the drive to perform a current-limit stop and set the
appropriate fault bit, in response this event
Default:
Options:
2
0
1
2
3
4
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
381 PreChrg Err Cnfg
Enter a value to configure the drive's response to a Precharge Error exception event.
0 “Ignore” Configures the drive to continue running, as normal, when this event occurs
1 “Alarm” - Configures the drive to continue running and set the appropriate alarm bit
when this event occurs
2 “FltCoastStop” - Configures the drive to perform a coast stop and set the appropriate
fault bit, in response this event
Default:
Options:
2
0
1
2
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”