2. Secure a M10 insulated standoff (larger size) to the bracket on the mounting
rail using a M10x12 bolt and flat and lock washer as shown below.
Important:The standoff must be secured to the hole in the bracket closest to
the mounting rail.
Step 6: Assemble the DC–
Bus Bars
Identify the following parts:
M10 Insulated Standoff (1 - larger size) and hardware
Long common Bus Bar (1)
Short common Bus Bar (1)
Z-shaped Bus Bar
1. Secure a M10 insulated standoff to the front of the longest bus bar using a
M10x16 bolt and flat and lock washer as shown below.
Install in hole closest to rail
Front side