Specifications
Category PowerFlex 700H PowerFlex 700S
Agency
Certification
Listed to UL 508C and CAN/CSA-C2.2 No. 14-M91. UL and cUL Listed to UL 508C and CAN/CSA - 22.2 No. 14-95.
Marked for all applicable European Directives
(1)
EMC Directive (89/336/EEC)
Emissions:
• EN 61800-3 Adjustable Speed electrical power drive systems
Low Voltage Directive (73/23/EEC)
• EN 50178 Electronic Equipment for use in Power Installations
Marked for all applicable European Directives
EMC Directive (89/336/EEC)
Emissions:
• EN 61800-3 Adjustable Speed electrical power drive systems Part 3
Low Voltage Directive (73/23/EEC)
• EN 50178 Electronic Equipment for use in Power Installations
Certified to AS/NZS, 1997 Group 1, Class A. Certified to AS/NZS, 1997 Group 1, Class A.
Certified to ATEX directive 94/9/EC. Group II Category (2) GD Applications
with ATEX Approved Motors. Refer to Appendix E Instructions for ATEX
Approved PowerFlex 700H Drives in Group II Category (2) Applications with
ATEX Approved Motors on page 203
for more information.
Certified to ATEX directive 94/9/EC. Group II Category (2) GD Applications with
ATEX Approved Motors. PowerFlex 700S Phase II Control drives only. Refer to
Appendix E ATEX Approved PowerFlex 700S, Phase II Drives in Group II Category
(2) Applications with ATEX Approved Motors, in publication 20D-PM001 for more
information.
(not applicable) TUV functional safety report only (no FS mark on the label)
The drive is also designed to meet the following specifications:
• NFPA 70 - US National Electrical Code
• NEMA ICS 7.1 - Safety standards for Construction and Guide for
Selection, Installation and Operation of Adjustable Speed Drive
Systems.
• IEC 146 - International Electrical Code.
The drive is designed to meet applicable requirements of the following codes/
standards:
• IEC 61800-2 Adjustable speed electrical power drive systems - General
requirements
• IEC 61800-5-1 Adjustable speed electrical power drive systems - Safety
requirements
• NFPA 70 - US National Electrical Code
(1) Applied noise impulses may be counted in addition to the standard pulse train causing erroneously high [Pulse Freq] readings.
N223
II 2 G/D
TUV
Rheinland
Product Safety
.
.
Production inspected
W
E
C
TUV
Rheinland
..
Functional
Safety
Bauart geprüft
Type approved
EN 50178