Manual
148 Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
Chapter 10 Frame 14 Mechanical Installation
Insulate Terminal X4 on the Rectifier Circuit Board
Follow the steps below to insulate terminal X4 onFigure 60 on page 141 the
rectifier circuit board for each converter unit (see for rectifier board location).
Task Description
Remove the screw from the X4 connection on the rectifier circuit board.
Insulate the top and bottom of the X4 connection on the rectifier circuit board.
IMPORTANT
Do not install the screw and washer that was removed from this connection.
A
B
X1
X4
X41
X1
X4
X41
Rectifying Circuit
Board
Jumper
Side View of Rectifying
Structure
A
B