Chapter 10 Frame 14 Mechanical Installation
Installation on an Ungrounded Distribution System or High Resistive
Ground
Must move the common mode jumper(s) to the disconnected position -
see Move the Common Mode Jumper(s) to the Disconnected Position on
page 147
.
Should insulate terminal X4 on the Rectifier circuit board - see Insulate
Terminal X4 on the Rectifier Circuit Board on page 148
.
If you are installing a 600/690V AC input drive on an ungrounded distribution
system or high resistive ground, you:
Must move the common mode jumper(s) to the disconnected position -
see Move the Common Mode Jumper(s) to the Disconnected Position on
page 147
.
Must insulate terminal X4 on the Rectifier circuit board - see Insulate
Terminal X4 on the Rectifier Circuit Board on page 148
.
Installation on a Grounded B Phase Delta System
If you are installing a drive on a grounded B phase Delta system, you:
Must move the common mode jumper(s) to the disconnected position -
see Move the Common Mode Jumper(s) to the Disconnected Position on
page 147
.
Must insulate terminal X4 on the Rectifier circuit board - see Insulate
Terminal X4 on the Rectifier Circuit Board on page 148
.