Chapter 9 Frame 13 Mechanical Installation
Table 29 - Power Terminal Specifications
Figure 53 - Power Terminal Locations
No. Name Description Wire Size Range
(1)(2)
Torque Terminal Bolt Size
(3)(4)
Maximum Minimum Recommended
1 Input Power Terminal Block
(1)
L1, L2, L3
Input power 300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 Nm
(354 lbin)
M12
2 Output Power Terminal Block
(3)
U/T1, V/T2, W/T3
Motor connections 300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N
m
(354 lb
in)
M12
3 SHLD Terminal, PE, Motor Ground
(3)
Terminating point for wiring shields 300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 Nm
(354 lbin)
M10
4 DC Bus
(3)
(3 Terminals; DC–, DC+)
DC input or external brake 300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 Nm
(354 lbin)
M12
(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2) Do Not exceed maximum wire size. Parallel connections may be required.
(3) These connections are bus bar type terminations and require the use of lug type connectors.
(4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.