120 Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
Chapter 9 Frame 13 Mechanical Installation
Minimum Mounting
Clearances
Operating Temperatures
Frame 13 drives require a minimum of 4200 m3/h (2472 cfm) of cooling air for
the inverter unit and 1150 m
3
/h (677 cfm) of cooling air for each converter unit.
800 mm
(31.50 in.) Min.
200 mm
(8.0 in.) Min.
1600 mm, Style “A” Enclosure Shown.
PowerFlex
Drive
Voltage Class Amp Rating Surrounding Air Temperature
Normal Duty Heavy Duty
700H All All 0…40° C (32…104° F) 0…40° C (32…104° F)
700S 400/480V AC
(540/650V DC)
All 0…40° C (32…104° F) 0…40° C (32…104° F)
600/690V AC
(810/932V DC)
920, 1030 0…40° C (32…104° F) 0…40° C (32…104° F)
600/690V AC
(810/932V DC)
1180 0…35° C (32…95° F) 0…35° C (32…95° F)