Manual

102 Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
Chapter 8 Frame 12 Mechanical Installation
Figure 38 - Enclosure Code B (NEMA/UL Type 1, IP21) and K (NEMA/UL Type 1, IP21 w/Conformal
Coat)
Operating Temperatures
Frame 12 drives require a minimum of 5200 m
3
/h (3060 cfm) of cooling air.
200 mm
(8.0 in.) Min.
Powerful Performance, Flexible Control.
838 mm
(33.0 in.) Min.
Powerful Performance, Flexible Control.
PowerFlex
Drive
Voltage Class Amp Rating Surrounding Air Temperature
Normal Duty Heavy Duty
700H 400/480V AC
(540/650V DC)
820, 920 0…40° C (32…104° F) 0…40° C (32…104° F)
400/480V AC
(540/650V DC)
1030 0…40° C (32…104° F) 0…35° C (32…95° F)
600/690V AC
(810/932V DC)
820, 920 0…40° C (32…104° F) 0…40° C (32…104° F)
600/690V AC
(810/932V DC)
1030 0…35° C (32…95° F040° C (32…104° F)
700S 400/480V AC
(540/650V DC)
820, 920 0…40° C (32…104° F) 0…40° C (32…104° F)
400/480V AC
(540/650V DC)
1030 0…40° C (32…104° F) 0…35° C (32…95° F
600/690V AC
(810/932V DC)
820, 920 0…40° C (32…104° F) 0…40° C (32…104° F)
600/690V AC
(810/932V DC)
1030 0…35° C (32…95° F035° C (32…95° F