User Manual

8 Rockwell Automation Publication PFLEX-IN025B-EN-P - September 2011
PowerFlex 700H and 700S AC Drives Frame 10 and 12 Main Fan Capacitor Replacement Kit
2. Remove the two M5 POZIDRIV screws that secure the front of the fan
inverter to the drive. Tightening torque for re-assembly is 4 N
m
(35 lb
in).
3. Disconnect the fan motor cable under the fan inverter.
4. Remove the four M5 POZIDRIV screws that secure the bottom of the fan
inverter to the drive. Tightening torque for re-assembly is 4 N
m
(35 lb
in).
Remove two screws from
front of inverter
Remove screws from
bottom of inverter
Remove screws from
bottom of inverter
Disconnect fan motor
cable connector
Left-hand side fan inverter shown