Installation Instructions - Frames 7…10 User Manual

Rockwell Automation Publication 20B-IN014H-EN-P - June 2013 75
PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
Manually Clearing Faults
Step Key(s)
1. Press Esc to acknowledge the fault. The fault information is removed so that you can use the
Human Interface Module (HIM).
2. Address the condition that caused the fault.
3. The cause must be corrected before the fault can be cleared.
4. After corrective action has been taken, clear the fault by one of these methods:
Press Stop
Cycle drive power
Set parameter 240 [Fault Clear] to “1.
“Clear Faults” on the Human Interface Module (HIM) Diagnostic menu.
Esc