Installation Instructions - Frames 7…10 User Manual

Rockwell Automation Publication 20B-IN014H-EN-P - June 2013 51
PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
I/O Terminal Designations
No. Signal
Factory
Default
Description
Related
Param.
1Analog In 1 ()
(1)
(1) Important: 0…20mA operation requires a jumper at terminals 17 & 18 (or 19 & 20). Drive damage can occur if jumper is not
installed.
(3)
(3) These inputs/outputs are dependant on a number of parameters (see “Related Parameters”).
Isolated
(4)
, bipolar, differential, ±10V/4-20mA, 11 bit & sign, 88k
ohm input impedance. For 4-20mA, a jumper must be installed at
terminals 17 & 18 (or 19 & 20).
(4) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode
immunity.
320…
327
2Analog In 1 (+)
(1)
3Analog In 2 ()
(1)
4Analog In 2 (+)
(1)
5 Pot Common For (+) and (–) 10V pot references.
6Analog Out 1 ()
(3)
Bipolar (current output is not bipolar), ±10V/4-20mA, 11 bit & sign,
voltage mode - limit current to 5 mA. Current mode - max. load
resistance is 400 ohms.
340…
347
7Analog Out 1 (+)
8Analog Out 2 ()
9Analog Out 2 (+)
10 HW PTC Input 1 1.8k ohm PTC, Internal 3.32k ohm pull-up resistor 238, 259
11 Digital Out 1 – N.C.
(2)
(2) Contacts in unpowered state. Any relay programmed as Fault or Alarm energizes (picks up) when power is applied to the drive and
deenergizes (drops out) when a fault or alarm exists. Relays selected for other functions energize only when that condition exists
and deenergize when condition is removed.
Fault Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10mA
380…
391
12 Digital Out 1 Common
13 Digital Out 1 – N.O.
(2)
NOT Fault
14 Digital Out 2 – N.C.
(2)
NOT Run
15 Digital Out 2/3 Com.
16 Digital Out 3 – N.O.
(2)
Run
17 Current In Jumper
(1)
Analog In 1
Placing a jumper across terminals 17 & 18 (or 19 & 20) configures that
analog input for current.
18
19 Current In Jumper
(1)
Analog In 2
20
21 –10V Pot Reference 2k ohm minimum load.
22 +10V Pot Reference
23 HW PTC Input 2 See above
24 +24VDC
(5)
Drive supplied logic input power.
(5)
(5) 150mA maximum Load. Not present on 115V versions.
25 Digital In Common
26 24V Common
(5)
Common for internal power supply.
27 Digital In 1 Stop - CF 115V AC, 50/60 Hz
- Control & I/O Cat. No. option D
Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC
24V DC
- Control & I/O Cat. No. option C
Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC
11.2 mA DC
361…
366
28 Digital In 2 Start
29 Digital In 3 Auto/Man.
30 Digital In 4 Speed Sel 1
31 Digital In 5 Speed Sel 2
32 Digital In 6/Hardware
Enable, see pg. 54
Speed Sel 3
33 Digital Out 4 – N.C. Fault Dedicated fault output - Not user configurable. Relay energizes (picks
up) when power is applied to the drive and deenergizes (drops out)
when a fault exists. See Terminals 11-16 for specs.
34 Digital Out 4 Common
35 Digital Out 4 – N.O. NOT Fault
PS+ Aux. Control Power (+) Refer to page 39
.
PS- Aux. Control Power (–) Refer to page 39
.
PE PE Ground PE Ground
PE PE Ground PE Ground