Installation Instructions - Frames 7â¦10 User Manual
Rockwell Automation Publication 20B-IN014H-EN-P - June 2013 51
PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
I/O Terminal Designations
No. Signal
Factory
Default
Description
Related
Param.
1Analog In 1 (–)
(1)
(1) Important: 0…20mA operation requires a jumper at terminals 17 & 18 (or 19 & 20). Drive damage can occur if jumper is not
installed.
(3)
(3) These inputs/outputs are dependant on a number of parameters (see “Related Parameters”).
Isolated
(4)
, bipolar, differential, ±10V/4-20mA, 11 bit & sign, 88k
ohm input impedance. For 4-20mA, a jumper must be installed at
terminals 17 & 18 (or 19 & 20).
(4) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode
immunity.
320…
327
2Analog In 1 (+)
(1)
3Analog In 2 (–)
(1)
4Analog In 2 (+)
(1)
5 Pot Common – For (+) and (–) 10V pot references.
6Analog Out 1 (–)
(3)
Bipolar (current output is not bipolar), ±10V/4-20mA, 11 bit & sign,
voltage mode - limit current to 5 mA. Current mode - max. load
resistance is 400 ohms.
340…
347
7Analog Out 1 (+)
8Analog Out 2 (–)
9Analog Out 2 (+)
10 HW PTC Input 1 – 1.8k ohm PTC, Internal 3.32k ohm pull-up resistor 238, 259
11 Digital Out 1 – N.C.
(2)
(2) Contacts in unpowered state. Any relay programmed as Fault or Alarm energizes (picks up) when power is applied to the drive and
deenergizes (drops out) when a fault or alarm exists. Relays selected for other functions energize only when that condition exists
and deenergize when condition is removed.
Fault Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10mA
380…
391
12 Digital Out 1 Common
13 Digital Out 1 – N.O.
(2)
NOT Fault
14 Digital Out 2 – N.C.
(2)
NOT Run
15 Digital Out 2/3 Com.
16 Digital Out 3 – N.O.
(2)
Run
17 Current In Jumper
(1)
–
Analog In 1
Placing a jumper across terminals 17 & 18 (or 19 & 20) configures that
analog input for current.
18
19 Current In Jumper
(1)
–
Analog In 2
20
21 –10V Pot Reference – 2k ohm minimum load.
22 +10V Pot Reference –
23 HW PTC Input 2 – See above
24 +24VDC
(5)
– Drive supplied logic input power.
(5)
(5) 150mA maximum Load. Not present on 115V versions.
25 Digital In Common –
26 24V Common
(5)
– Common for internal power supply.
27 Digital In 1 Stop - CF 115V AC, 50/60 Hz
- Control & I/O Cat. No. option D
Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC
24V DC
- Control & I/O Cat. No. option C
Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC
11.2 mA DC
361…
366
28 Digital In 2 Start
29 Digital In 3 Auto/Man.
30 Digital In 4 Speed Sel 1
31 Digital In 5 Speed Sel 2
32 Digital In 6/Hardware
Enable, see pg. 54
Speed Sel 3
33 Digital Out 4 – N.C. Fault Dedicated fault output - Not user configurable. Relay energizes (picks
up) when power is applied to the drive and deenergizes (drops out)
when a fault exists. See Terminals 11-16 for specs.
34 Digital Out 4 Common
35 Digital Out 4 – N.O. NOT Fault
PS+ Aux. Control Power (+) Refer to page 39
.
PS- Aux. Control Power (–) Refer to page 39
.
PE PE Ground PE Ground
PE PE Ground PE Ground
1