Installation Instructions - Frames 7â¦10 User Manual
Rockwell Automation Publication 20B-IN014H-EN-P - June 2013 37
PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
Frame 10
Fan/Blower Terminal Blocks - Frames 8…10
Fan Transformer Specifications/Fusing
Three-Phase Blower Fusing
Drive
Type Enclosure
Rating
(120VAC)
No. of
Fans Connect at …
DC
Input
IP00, NEMA/UL Type Open 1000 VA 2 TB9 & 10
Requires user supplied 120V AC. See page 11
for TB
locations and page 37
for terminal designations.
IP20, NEMA/UL Type 1 1000 VA 2
AC
Input
IP00, NEMA/UL Type Open 1000 VA 3 TB9, 10 & 12
Requires user supplied 120V AC. See page 11
for TB
locations and page 37
for terminal designations.
IP20, NEMA/UL Type 1 1000 VA 3 TB9, 10 & 12
A transformer (see
page 11
) matches the
input line voltage to
the internal fan
voltage. If line voltage
is different than the
voltage class specified
on the drive
nameplate, the
transformer taps may
require changing.
Frame Rating
Recommended Fuses
Primary (Quantity 2) Secondary (Quantity 1)
8 & 9 500 VA 2.8A, 600V AC, KLDR/ATQR Type 6.25A, 250V AC, Time Delay
10 1000 VA 6A, 600V AC, KLDR/ATQR Type 9A, 250V AC, Time Delay
Frame Recommended Fuses (Quantity 3)
9 5A, 600V AC, Time Delay
Input Line Voltage
480/400V AC, 50/60 Hz
F2
H3
480 400
F3
to TB9
JMP
0
115 0
F1
H2H1
X1 XF X2
120V
120V
N
120V
AC Input
N
PE
PE
7
Line
Neutral
To Fan(s)
Ground
NC
RTS
Frame 10, AC Input, IP20 Only
120V
120V
N
120V
AC Input
N
PE
PE
7
Line
Neutral
To Fan(s)
Ground
NC
TB9, TB10 TB12
Frame 9 Only
Blower TB
Frames 8…10