Installation Instructions - Frames 7…10 User Manual

Rockwell Automation Publication 20B-IN014H-EN-P - June 2013 33
PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
Typical Location - Phase Select Jumper
Table 4 - 380…480 Volt Single-Phase AC Input Ratings
Power Terminal Blocks
Refer to pages 8 through 11 for typical locations.
480V Single-Phase AC Input 380…400V Single-Phase AC Input
Temp.
Drive
Catalog
Number
Frame
Hp
Rating
Input
Amps
Three-Phase
Output
Drive
Catalog
Number
Frame
kW
Ratin
g
Input
Amps
Three-Phase
Output
V AC Amps V AC Amps °C
20BD292 7 125 237.4 0-460 146 20BC292 7 80 247.7 0-400 146 25
20BD325 7 125 264.3 0-460 162.5 20BC325 7 90 275.7 0-400 162.5 25
ATTENTION: National Codes and standards (NEC, VDE, BSI etc.) and local codes
outline provisions for safely installing electrical equipment. Installation must
comply with specifications regarding wire types, conductor sizes, branch circuit
protection and disconnect devices. Failure to do so can result in personal injury
and/or equipment damage.
Name Frame Description
Wire Size Range
see Note
(2)
(2) Maximum/minimum sizes that the terminal block accepts - these are not recommendations.
Torque
Maximum Minimum Maximum Recommended
Power
Terminal Block
7Input power, DC+,
DC–, PE, motor
connections
150.0 mm2
(300 MCM)
see Note
(3)
(3) If can be necessary to connect multiple wires in parallel to these terminals by using multiple lugs.
2.5 mm
2
(14 AWG)
2.7 N•m
(24 lb•in)
2.7 N•m
(24 lb•in)
8…10 Input power, DC+,
DC–, PE, motor
connections
300.0 mm2
(600 MCM)
see Note
(3)
2.5 mm
2
(14 AWG)
10.0 N•m
(87 lb•in)
10.0 N•m
(87 lb•in)
AUX Terminal
Block
(1)
7…10 Auxiliary Control
Voltage
PS+, PS–
(1)
(1) External control power - select drives only, see Auxiliary Control Power Supply on page 39 for details.
4.0 mm
2
(12 AWG)
0.049 mm
2
(30 AWG)
0.6 N•m
(5.3 lb•in)
0.6 N•m
(5.3 lb•in)
Fan Terminal
Block
7User Supplied Fan
Voltage
4.0 mm
2
(12 AWG)
0.5 mm
2
(22 AWG)
0.9 N•m
(8.0 lb•in)
0.6 N•m
(5.3 lb•in)
8…10 4.0 mm
2
(12 AWG)
0.5 mm
2
(22 AWG)
0.6 N•m
(5.3 lb•in)
0.6 N•m
(5.3 lb•in)
LINE
TYPE
SPARE 1
SPARE 2
3-PH 1-PH
JP1 JP2 JP3
1-PH 3-PH
LINE TYPE
3
3
3
AC Input
Precharge
Board