Rockwell Automation Publication 20D-UM007G-EN-P - March 2012 25
Installation and Wiring Chapter 2
Wiring
Important points to remember about wiring:
Always use tinned copper wire.
Wire with an insulation rating of 600V or greater is recommended.
Control wires should be separated from power wires by at least 0.3 meters
(1 foot).
All control wires should be shielded cable with the shield earthed on one
end of the cable.
Table 1 - DriveGuard Safe Torque Off Option Terminal Block Specifications
Table 2 - Wire Types
Table 3 - DriveGuard Safe Torque Off Option Terminals Description
Wire Size Range
(1)
(1) Maximum / minimum that the terminal block will accept - these are not
recommendations.
Torque
Maximum Minimum Maximum Recommended
1.5 mm
2
(16 AWG)
0.14 mm
2
(26 AWG)
0.25 N•m
(2.2 lb•in)
0.22 N•m
(1.9 lb•in)
Wire Type(s) Description
Minimum
Insulation Rating
Unshielded Per US NEC or applicable
national or local code
NOT RECOMMENDED 300V,
60 degrees C
(140 degrees F)
Shielded Multi-conductor shielded cable
such as Belden 8770(or equiv.)
0.750 mm
2
(18AWG),
3 conductor, shielded.
No. Signal Description
1 +24V DC Connections for user-supplied power
to energize coil.
33.3 mA typical, 55 mA maximum.
2 24V Common
3 Monitor - N.C. Normally closed contacts for
monitoring relay status.
Maximum Resistive Load:
250V AC / 30V DC / 50 VA / 60 Watts
Maximum Inductive Load:
250V AC / 30V DC / 25 VA / 30 Watts
4 Common - N.C.