Installation Instructions - Frames 0…6

8 Rockwell Automation Publication 20B-IN019E-EN-P - July 2013
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Essential Requirements for CE Compliance
Conditions 1…6 listed below must be satisfied for PowerFlex drives to meet the
requirements of EN61800-3.
1. Standard PowerFlex 700 CE compatible Drive.
2. Review important precautions/attention statements throughout this
publication and the User Manual before installing the drive.
3. Grounding as described in this publication and the User Manual.
4. Output power, control (I/O) and signal wiring must be braided, shielded
cable with a coverage of 75% or better, metal conduit, or equivalent
attenuation.
5. All shielded cables must terminate with the proper shielded connector.
6. The following conditions:
First Environment Restricted Distribution - For any drive and option a
filter is required for motor cable lengths greater than 150 m (492 ft.).
Second Environment (Industrial) - Motor cable is limited to 30 m (98
ft.) for installations without additional external line filters.
External filters for First Environment installations and increasing motor cable
lengths in Second Environment installations are available. Roxburgh models
KMFA (RF3 for UL installations) and MIF or Schaffner FN3258 and FN258
models are recommended. Refer to Tabl e 1
and http://www.dem-uk.com and
http://www.mtecorp.com
(USA) or http://www.schaffner.com, respectively.
Table 1 - PowerFlex 700 Recommended Filters
Manufacturer Frame
Manufacturer Part
No.
Class A
(Meters)
Class B
(Meters)
Deltron 0 MIF316 150
KMF318A 100
1 KMF325A 150
2 KMF350A 200 150
2 without DC Common Mode Capacitor KMF350A 176 150
3 KMF370A 150 100
3 without DC Common Mode Capacitor KMF370A 150 100
Schaffner 0 FN358-16-45
1 FN358-30-47
2 FN358-42-47 50
2 without DC Common Mode Capacitor FN358-42-47 150
3 FN358-75-52 100
3 without DC Common Mode Capacitor FN358-75-52 150