Installation Instructions - Frames 0…6

Rockwell Automation Publication 20B-IN019E-EN-P - July 2013 73
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Table 11 - Abbreviated Alarm Listing
Alarm
No.
Type
(1)
(1) See the User Manual for a description of alarm types.
Description
Dig In
ConflictA
17
Digital input functions are in conflict. Combinations marked with a “ ” cause an alarm.
Dig In
ConflictB
18
A digital Start input has been configured without a Stop input or other functions are in conflict.
Combinations that conflict are marked with a “ ” and cause an alarm.
Dig In
ConflictC
19
More than one physical input has been configured to the same input function. Multiple
configurations are not allowed for the following input functions.
Forward/Reverse Run Reverse Bus Regulation Mode B
Speed Select 1 Jog Forward Acc2 / Dec2
Speed Select 2 Jog Reverse Accel 2
Speed Select 3 Run Decel 2
Run Forward Stop Mode B
TB Man
Ref Cflct
30
Occurs when:
Auto/Manual” is selected (default) for [Digital In3 Sel], parameter 363 and
[TB Man Ref Sel], parameter 96 has been reprogrammed.
No other use for the selected analog input can be programmed.
Example: If [TB Man Ref Sel] is reprogrammed to Analog In 2,” all of the factory default uses
for “Analog In 2” must be reprogrammed (such as parameters 90, 117, 128 and 179). Refer to
the Auto/Manual Examples section of the PowerFlex 700 User Manual.
To correct:
Verify/reprogram the parameters that reference an analog input or
Reprogram [Digital In3] to another function or “Unused.
Acc2/Dec2 Accel 2 Decel 2 Jog 1/2 Jog Fwd Jog Rev Fwd/Rev
Acc2/Dec2
Accel 2
Decel 2
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev
Start Stop-CF Run Run Fwd Run Rev Jog 1/2 Jog Fwd Jog Rev Fwd/Rev
Start
Stop-CF
Run
Run Fwd
Run Rev
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev