Installation Instructions - Frames 0…6

70 Rockwell Automation Publication 20B-IN019E-EN-P - July 2013
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Running an Assisted Start Up
The Assisted start-up routine prompts you to input required information. Access
Assisted Start Up by selecting “Start Up” from the Main Menu.
To perform an Assisted Start-Up
Drive Status Indicators
IMPORTANT
This start-up routine requires an LCD HIM.
Step Key(s) Example LCD Displays
1. In the Main Menu, press the Up Arrow or
Down Arrow to scroll to “Start Up”.
2. Press Enter.
IMPORTANT
Done/Exit must be selected upon completion of the Start Up routine in order
for any Start Up/Autotune data to be saved.
Name Color State Description
Green Steady Illuminates when power is applied to the drive.
Green Flashing Drive ready, but not running and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing, Drive
Stopped
An inhibit condition exists, the drive cannot be started. Check
parameter 214 [Start Inhibits].
Flashing, Drive
Running
An intermittent type 1 alarm condition is occurring.
Check parameter 211 [Drive Alarm 1].
Steady,
Drive Running
A continuous type 1 alarm condition exists.
Check parameter 211 [Drive Alarm 1].
Red Flashing A fault has occurred.
Steady A non-resettable fault has occurred.
Refer to the Communication
Adapter User Manual.
Status of DPI port internal communications (if present).
Status of communications module (when installed).
Status of network (if connected).
Status of secondary network (if connected).
F-> Stopped Auto
0.0
Hz
Main Menu:
Memory Storage
Start Up
Preferences