Installation Instructions - Frames 0…6

Rockwell Automation Publication 20B-IN019E-EN-P - July 2013 57
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Hardware Enable Circuitry (Vector Control Only)
By default, the user can program a digital input as an Enable input. The status of
this input is interpreted by drive software
. If the application requires the drive to
be disabled without
software interpretation, a “dedicated” hardware enable
configuration can be utilized. This is done by removing a jumper and wiring the
enable input to “Digital In 6.
1. Remove the I/O Control Cassette & cover as
described on page 53
.
2. Locate & remove Jumper J10 on the Main
Control Board (see diagram).
3. Re-assemble cassette.
4. Wire Enable to “Digital In 6” (see page 54
).
5. Verify that [Digital In6 Sel], parameter 366 is
set to “1, Enable.
2-Wire Control
Reversing
(1)
External supply
(I/O Board dependent)
Set Digital Input:#1:
Parameter 361 = “8, Run Forward”
Set Digital Input #2:
Parameter 362 = “9, Run Reverse
3-Wire Control
Internal supply
No Changes Required
3-Wire Control
External supply (I/O Board
dependent). Requires 3-wire
functions only ([Digital In1
Sel]). Using 2-wire selections
causes a type 2 alarm.
No Changes Required
Digital Input
PLC Output Card (Board
dependent).
No Changes Required
Digital Output
Relays (two at terminals
14…16) shown in powered
state with drive faulted. See
page 54
and page 55.
Select Source to Activate:
Parameters 380/384
Enable Input •Configure with parameter 366
For dedicated hardware Enable:
Remove Jumper J10 (see below)
(1) Refer to the Attention statement on page 52 for important bipolar wiring information.
(2) Important: Programming inputs for 2 wire control deactivates all HIM Start buttons unless parameter 192, [Save HIM Ref], bit 1
[Manual Mode] = “1.” This allows the HIM to control Start and Jog.
Input/Output Connection Example Required Parameter Changes
25
27
28
Run Rev.
Run Fwd.
115V
/
+24V
Neutral/
Common
Start
24
25
26
27
28
Stop
Start
25
27
28
Stop
115V/
+24V
Neutral/
Common
25
27
28
Control from
Prog. Controller
Neutral/
Common
10k Ohm, 2 Watt
Power Source
11
12
13
14
15
16
Fault
NOT Fault
NOT Run
Run
or
32
ENA
BLE
JUMP
ER
J10