Installation Instructions - Frames 0â¦6
Rockwell Automation Publication 20B-IN019E-EN-P - July 2013 55
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Standard Control Option I/O Terminal Designations
No. Signal
Factory
Default Description
Related
Param.
1 Anlg Volts In 1 (–)
(2)
Isolated
(3)
, bipolar, differential, ±10V, 11 bit & sign,
88k ohm input impedance.
320 -
327
2 Anlg Volts In 1 (+)
3 Anlg Volts In 2 (–)
(2)
Isolated
(4)
, bipolar, differential, ±10V, 11 bit & sign,
88k ohm input impedance.
4 Anlg Volts In 2 (+)
5 Pot Common – For (+) and (–) 10V pot references.
6Anlg Volts Out 1 (–)
(2)
Bipolar, ±10V, 11 bit & sign, 2k ohm minimum load. 340 -
344
7Anlg Volts Out 1 (+)
8 Anlg Current Out 1 (–)
(2)
4-20mA, 11 bit & sign, 400 ohm maximum load.
9 Anlg Current Out 1 (+)
10 Reserved for Future Use
11 Digital Out 1 – N.C.
(1)
Fault Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10mA
380 -
387
12 Digital Out 1 Common
13 Digital Out 1 – N.O.
(1)
NOT Fault
14 Digital Out 2 – N.C.
(1)
NOT Run
15 Digital Out 2 Common
16 Digital Out 2 – N.O.
(1)
Run
17 Anlg Current In 1 (–)
(2)
Isolated
(3)
,
4-20 mA
, 11 bit & sign, 124 ohm input
impedance.
320 -
327
18 Anlg Current In 1 (+)
19 Anlg Current In 2 (–)
(2)
Isolated
(4)
, 4-20 mA, 11 bit & sign, 124 ohm input
impedance.
20 Anlg Current In 2 (+)
21 –10VDC Pot Ref. – 2k ohm minimum.
22 +10VDC Pot Ref. –
23 Reserved for Future Use
24 +24VDC
(5)
– Drive supplied logic input power.
(5)
25 Digital In Common –
26 24V Common
(5)
– Common for internal power supply.
27 Digital In 1 Stop - CF 115V AC, 50/60 Hz
- Control & I/O Cat. No. option B
Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC, 5.0 mA
24V AC/DC, 50/60 Hz
- Control & I/O Cat. No. option A
Opto isolated
Low State: less than 5V AC/DC
High State: greater than 20V AC/DC
11.2 mA DC
Digital Input Impedance: 35k ohm
361 -
366
28 Digital In 2 Start
29 Digital In 3 Auto/Man.
30 Digital In 4 Speed Sel 1
31 Digital In 5 Speed Sel 2
32 Digital In 6 Speed Sel 3
(1) Contacts in unpowered state. Any relay programmed as Fault or Alarm energizes (picks up) when power is applied to drive and deenergize
(drop out) when a fault or alarm exists. Relays selected for other functions energize only when that condition exists and deenergizes when
condition is removed.
(2) These inputs/outputs are dependant on a number of parameters. See “Related Parameters.”
(3) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
(4) Differential Isolation - External source must be less than 10V with respect to PE.
(5) 150 mA
maximum load designed to power digital inputs only. Not present on 115V versions.