Installation Instructions - Frames 0â¦6
54 Rockwell Automation Publication 20B-IN019E-EN-P - July 2013
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Vector Control Option I/O Terminal Designations
No. Signal
Factory
Default Description
Related
Param.
1Analog In 1 (–)
(1) (4)
Isolated
(5)
, bipolar, differential, ±10V/0-20 mA, 11
bit & sign. For 0-20 mA, a jumper must be installed at
terminals 17 & 18 (or 19 & 20). 88k ohm input
impedance when configured for volt. & 95.3 ohm for
current
320 -
327
2Analog In 1 (+)
(1)
3Analog In 2 (–)
(1)
4Analog In 2 (+)
(1)
5 Pot Common – For (+) and (–) 10V pot references.
6 Analog Out 1 (–)
(4)
Single-ended bipolar (current output is not bipolar),
±10V/0-20 mA, 11 bit & sign, Voltage mode - limit
current to 5 mA. Current mode - max. load is 400
ohms.
340 -
347
7 Analog Out 1 (+)
8 Analog Out 2 (–)
9 Analog Out 2 (+)
10 HW PTC Input 1 – 1.8k ohm PTC, Internal 3.32k ohm pull-up resistor 238 259
11 Digital Out 1 – N.C.
(2)
Fault Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10 mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10 mA
380 -
391
12 Digital Out 1 Common
13 Digital Out 1 – N.O.
(2)
NOT Fault
14 Digital Out 2 – N.C.
(2)
NOT Run
15 Digital Out 2/3 Com.
16 Digital Out 3 – N.O.
(2)
Run
17 Current In Jumper
(1)
–
Analog In 1
Placing a jumper across terminals 17 & 18 (or 19 &
20) configures that analog input for current.
320 -
327
18
19 Current In Jumper
(1)
–
Analog In 2
20
21 –10VDC Pot Ref. – 2k ohm minimum load.
22 +10VDC Pot Ref. –
23 HW PTC Input 2 – See above
24 +24VDC
(6)
– Drive supplied logic input power.
(6)
25 Digital In Common –
26 24V Common
(6)
– Common for internal power supply.
27 Digital In 1
(3)
Stop - CF 115V AC, 50/60 Hz - Control & I/O Cat. No. option D
Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC, 5.7 mA
24V DC
- Control & I/O Cat. No. option C
Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC, 10 mA DC Digital
Input Impedance: 21k ohm
361 -
366
28 Digital In 2
(3)
Start
29 Digital In 3
(3)
Auto/Man.
30 Digital In 4
(3)
Speed Sel 1
31 Digital In 5
(3)
Speed Sel 2
32 Digital In 6/Hardware
Enable
(3)
, see pg. 57
Speed Sel 3
(1) Important: 0…20 mA operation requires a jumper at terminals 17 & 18 (or 19 & 20). Drive damage can occur if jumper is not installed.
(2) Contacts in unpowered state. Any relay programmed as Fault or Alarm energizes (picks up) when power is applied to drive and deenergize
(drop out) when a fault or alarm exists. Relays selected for other functions energize only when that condition exists and deenergizes when
condition is removed.
(3) A 10k ohm, 2 watt burden resistor must be installed on each digital input when using a triac type device. The resistor is installed between each
digital input and neutral /common.
(4) These inputs/outputs are dependant on a number of parameters (see “Related Parameters”).
(5) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
(6) 150 mA maximum load designed to power digital inputs only. Not present on 115V versions.
1
16
32