Snubber Resistors
See Chapter 1 - Component Diagrams and Torque Specifications to locate
components in these instructions.
Remove Components
1. Read and follow the Safety Precautions on page 11 and Important Initial
Steps on page 12.
2. Remove safety shields and enclosure covers as needed.
3. Locate the Snubber Resistor(s) to be replaced.
4. Carefully label and disconnect all wires for the Snubber Resistor(s). See
AC Busbars on page 35
to locate the AC Busbar screws for the red wire(s).
5. Remove the Snubber Resistor(s) mounting screws.
6. Remove the Snubber Resistor(s) and dispose of properly.
Snubber Resistors (3) and Mounting Screws (2 each)
Snubber Board
J1 and J2 Connectors
Red Wire is connected to its Respective AC Busbar: R, S,
or T
R
S
T
R
S
T