Manual

Rockwell Automation Publication 20B-IN024C-EN-P - June 2012 47
Component Replacement Procedures Chapter 3
Capacitor Bank Fan
See Chapter 1 - Component Diagrams and Torque Specifications to locate the
component
detailed in these instructions.
Remove Components
1. Read and follow the Safety Precautions on page 12 and Important Initial
Steps on page 13.
2. Remove the stacking panel as detailed on
page 26
.
3. Label and disconnect all wires for the fan.
4. Remove the four mounting screws.
5. Remove the fan assembly.
Install Components
1. Install the new fan assembly. Torque the four mounting screws to 1.8 N•m
(16 lb•in).
2. Connect the wires.
3. Install the stacking panel as detailed on page 27
.
4. Replace all safety shields and enclosure covers before applying power to the
drive.
Four Mounting Screw