User Manual
Rockwell Automation Publication 20B-UM002G-EN-P - July 2014 93
Troubleshooting Chapter 2
Table 5 - Alarm Cross Reference
Start At PowerUp 4 1 [Start At PowerUp] is enabled. Drive can start at any time within 10 seconds of drive
powerup.
TB Man Ref Cflct 30 2 Occurs when:
• “Auto/Manual” is selected (default) for [Digital In3 Sel], parameter 363 and
• [TB Man Ref Sel], parameter 96 has been reprogrammed.
No other use for the selected analog input can be programmed.
Example: If [TB Man Ref Sel] is reprogrammed to “Analog In 2,” all of the factory default
uses for “Analog In 2” must be reprogramed (such as parameters 90, 117, 128 and 179).
To correct:
• Verify/reprogram the parameters that reference an analog input or
• Reprogram [Digital In3] to another function or “Unused.”
TorqProve Cflct 49 2 When [TorqProve Cnfg] is enabled, [Motor Cntl Sel], [Feedback Select] and [Motor Fdbk
Type] must be properly set (see page 115).
UnderVoltage 2 1 The bus voltage has dropped below a predetermined value.
VHz Neg Slope 24 2 [Torq Perf Mode] = “Custom V/Hz” & the V/Hz slope is negative.
Waking 11 1 The Wake timer is counting toward a value that will start the drive.
(1) See page 83 for a description of alarm types.
No.
(1)
(1) Alarm numbers not listed are reserved for future use.
Alarm No.
(1)
Alarm No.
(1)
Alarm
1 Precharge Active 15 Ground Warn 28 Ixo Vlt Rang
2UnderVoltage 16
(2)
(2) Firmware 6.002 and later only.
Brake Slipping 29 Sleep Config
3 Power Loss 17 Dig In ConflictA 30 TB Man Ref Cflct
4 Start At PowerUp 18Dig In ConflictB 31PTC Conflict
5 Analog in Loss 19 Dig In ConflictC 32 Brake Slipped
6 IntDBRes OvrHeat 20 Bipolar Conflict 33 AdjVoltRef Cflct
8 Drive OL Level 1 21 Motor Type Cflct 34 Home Not Set
9 Drive OL Level 2 22 NP Hz Conflict 38 DPI Port1 Loss
10 Decel Inhibt 23 MaxFreq Conflict 39 DPI Port2 Loss
11 Waking 24 VHz Neg Slope 40 DPI Port3 Loss
12 Motor Thermistor 25 IR Volts Range 49 Torq Prove Cflct
13 In Phase Loss 26 FluxAmpsRef Rang 50 Prof Step Cflct
14 Load Loss 27 Speed Ref Cflct 52 PI Config Conflict
Alarm
No.
Type
(1)
Description