Chapter 1 Programming and Parameters
INPUTS & OUTPUTS
Digital Outputs
392 [Dig Out Invert]
Inverts the selected digital output.
393 [Dig Out Param]
Selects the value that the mask ([Dig Out Mask])
will be applied to.
Default:
Options:
0
0
1
2-3
4-5
6
7
8-9
10
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
“PI Config
“PI Config
“PI Status”
“Drive Sts 1-2”
“DriveAlarm1-2“
“StartInhibit
“DigIn Status“
“DrvSts1/2Flt
AlrmSts1/2Flt
“LogicCmdRslt“
“Stop Owner
“Start Owner
“Jog Owner
“Dir Owner
“Ref Owner
Accel Owner
“Decel Owner
“FltRst Owner
“MOP Owner
“Local Owner
“Limit Status“
“PortMaskAct“
“WriteMaskAct
“LogicMaskAct“
“TorqProvCnfg“
“TorqProvSet
“TorqProvSts“
“Profile Sts“
“Profile Cmd“
394 [Dig Out Mask]
Sets the mask that is applied to the selected value in [Dig Out Param]. A bit (AND/OR) is applied,
which is selected by the [Digital Outx Sel]. All bits with zeros in the mask are ignored.
Example:
File
Group
No.
Parameter Name & Description
See page 16 for symbol descriptions
Values
Related
00x 0xxxxxxxxxxxx
10 01234567891112131415
1 = Inverted
0 = Not Inverted
x = Reserved
Bit #
Factory Default Bit Values
Digital Out1
Digital Out2
Digital Out3
0000000000000000
10 01234567891112131415
1 = Bit selected
0 = Bit Masked
x = Reserved
Bit #
Factory Default Bit Values
Mask OR: If Any bits in the value are set in the mask, then the output is On.
Mask AND: If All bits in the value are set in the mask then the output is On.
Selected Value 000011001 11100 00
Mask 00000000
1 00001 00
Result Output On
Selected Value 00001100
1 11100 00
Mask 00000000
1 00001 00