User Manual

58 Rockwell Automation Publication 20B-UM002G-EN-P - July 2014
Chapter 1 Programming and Parameters
COMMUNICATIONS
Datalinks
300
301
[Data In A1] - Link A Word 1
[Data In A2] - Link A Word 2
Parameter number whose value will be written
from a communications device data table. Value
will not be updated until drive is stopped.
Refer to your communications option manual for
datalink information.
Default:
Min/Max:
Units:
0 (0 = “Disabled”)
0/611
1
302
303
[Data In B1] - Link B Word 1
[Data In B2] - Link B Word 2
See [Data In A1] -
Link A Word 1 [Data In A2] -
Link A Word 2.
304
305
[Data In C1] - Link C Word 1
[Data In C2] - Link C Word 2
See [Data In A1] - Link A Word 1 [Data In A2] -
Link A Word 2.
306
307
[Data In D1] - Link D Word 1
[Data In D2] - Link D Word 2
Not available with Liquid-Cooled drives.
See [Data In A1] -
Link A Word 1 [Data In A2] -
Link A Word 2.
308 [HighRes Ref]
Used as a high resolution, 32 bit reference with
Datalinks.
–/+[Maximum Freq] or
–/+[Maximum Speed] = 32767 x 65536
Default:
Min/Max:
Units:
0
–/+2147418112
1
090
093
126
128
213
298
310
311
[Data Out A1] - Link A Word 1
[Data Out A2] - Link A Word 2
Parameter whose value will be written to a
communications device data table.
Default:
Min/Max:
Units:
0 (0 = “Disabled”)
0/611
1
312
313
[Data Out B1] - Link B Word 1
[Data Out B2] - Link B Word 2
See [Data Out A1] -
Link A Word 1 [Data Out
A2] - Link A Word 2.
314
315
[Data Out C1] - Link C Word 1
[Data Out C2] - Link C Word 2
See [Data Out A1] -
Link A Word 1 [Data Out
A2] - Link A Word 2.
316
317
[Data Out D1] - Link D Word 1
[Data Out D2] - Link D Word 2
See [Data Out A1] -
Link A Word 1 [Data Out
A2] - Link A Word 2.
Security
595 [Port Mask Act] Read Only
Bits 0-5 indicate status for DPI port communication. Bit 15 indicates when security software is
controlling the parameter.
596 [Write Mask Cfg]
Enables/disables write access (parameters, links, etc.) for DPI ports. Changes to this parameter
only become effective when power is cycled, the drive is reset or bit 15 of [Write Mask Actv],
transitions from “1” to “0.
File
Group
No.
Parameter Name & Description
See page 16 for symbol descriptions
Values
Related
v6
1111111xxxxxxxx0
10 01234567891112131415
1 = Active
0 = Not Active
x = Reserved
Bit #
Factory Default Bit Values
Host
DPI Port 1
DPI Port 2
DPI Port 3
DPI Port 4
DPI Port 5
DPI Port 6
(1)
Security
(1)
Firmware 6.002 and later.
111 x111xxxxxxxxx
10 01234567891112131415
1 = Write Permitted
0 = Read Only
x = Reserved
Bit #
Factory Default Bit Values
DPI Port 1
DPI Port 2
DPI Port 3
DPI Port 4
DPI Port 5
DPI Port 6
(1)
(1)
Firmware 6.002 and later.