User Manual
Rockwell Automation Publication 20B-UM002G-EN-P - July 2014 53
Programming and Parameters Chapter 1
UTILITY
Faults
244
246
248
250
252
254
256
258
[Fault 1 Time]
[Fault 2 Time]
[Fault 3 Time]
[Fault 4 Time]
[Fault 5 Time]
[Fault 6 Time]
[Fault 7 Time]
[Fault 8 Time]
Default:
Min/Max:
Units:
Read Only
0.0000/214748.3647 Hr
0.0001 Hr
242
The time between initial drive power up and the occurrence of the associated trip fault. Can be
compared to [Power Up Marker] for the time from the most recent power up.
[Fault x Time] – [Power Up Marker] = Time difference to the most recent power up. A negative
value indicates fault occurred before most recent power up. A positive value indicates fault
occurred after most recent power up.
To convert this value to the number days, hours, minutes and seconds, the following formula can
be used:
Fault x Time /24 hours = (# of days).(remaining time)
Remaining Time x 24 hours = (# of hours)
Remaining Time x 60 minutes = (# of minutes).(remaining time)
Remaining Time x 60 seconds = (# of seconds)
Result = (# of days).(# of hours).(# of minutes).(# of seconds)
Example: 1909.2390 Hrs / 1 Day/24 Hrs = 79.551625 Days
0.551625 Days x 24 Hrs/Day = 13.239 Hrs
0.239 Hrs x 60 Min/Hr = 14.34 Min
0.34 Min x 60 Sec/Min = 20.4 Secs
Alarms
259 [Alarm Config 1]
Enables/disables alarm conditions that will initiate an active drive alarm.
Description
OW Trq Level, bit 19For the Rod Torque Process Display to work, the Oil Well Torque Level must be
enabled.
261 [Alarm Clear]
Resets all [Alarm 1-8 Code] parameters to zero.
Default:
Options:
0
0
1
“Ready”
“Ready”
“Clr Alrm Que”
262
263
264
265
266
267
268
269
File
Group
No.
Parameter Name & Description
See page 16 for symbol descriptions
Values
Related
111111x11110000x
10 01234567891112131415
1 = Condition True
0 = Condition False
x = Reserved
Bit #
Prechrg Actv
UnderVoltage
Power Loss
Str At PwrUp
Anlg in Loss
IntDBRes OH
Drv OL Lvl 1
Drv OL Lvl 2
Decel Inhibt
Waking
Motor Therm
In PhaseLoss
Load Loss
Ground Warn
10001111xxxxxxxx
26 161718192021222324252728293031
1 = Condition True
0 = Condition False
x = Reserved
Bit #
Adj Volt Ref
Prof SetHome
PTC HW
DPI P1 Loss
(2)
DPI P2 Loss
(2)
DPI P3 Loss
(2)
OW Trq Level
Active Cnvtr
(1)
(1)
Firmware 6.002 and later.
(2)
Firmware 9.001 and later.