Rockwell Automation Publication 20B-UM002G-EN-P - July 2014 51
Programming and Parameters Chapter 1
UTILITY
Diagnostics
229 [Alarm 1 @ Fault]
Captures and displays [Drive Alarm 1] at the time of the last
fault.
Read Only 211
224
…
230
230 [Alarm 2 @ Fault]
Captures and displays [Drive Alarm 2] at the time of the last
fault.
Read Only 212
224
…
230
234
236
[Testpoint 1 Sel]
[Testpoint 2 Sel]
Selects the function whose value is displayed
value in [Testpoint x Data].
These are internal values that are not accessible
through parameters.
See Testpoint C odes and Functions
on page 96
for a listing of available codes and functions.
Default:
Min/Max:
Units:
499
0/65535
1
235
237
[Testpoint 1 Data]
[Testpoint 2 Data]
The present value of the function selected in
[Testpoint x Sel].
Default:
Min/Max:
Units:
Read Only
–/+2147483648
1
File
Group
No.
Parameter Name & Description
See page 16 for symbol descriptions
Values
Related
000000x000000000
10 01234567891112131415
1 = Condition True
0 = Condition False
x = Reserved
Bit #
Prechrg Actv
UnderVoltage
Power Loss
Str At PwrUp
Anlg in Loss
IntDBRes OH
Drv OL Lvl 1
Drv OL Lvl 2
Decel Inhibt
Waking
Motor Therm
In PhaseLoss
Load Loss
Ground Warn
Brk Slipped
00x 00000xxxxxxxx
26 161718192021222324252728293031
1 = Condition True
0 = Condition False
x = Reserved
Bit #
Adj Volt Ref
Prof SetHome
PTC HW
Active Cnvtr
(1)
(1)
Firmware 6.002 and later.
(2)
Firmware 9.001 and later.
DPI P1 Loss
(2)
DPI P2 Loss
(2)
DPI P3 Loss
(2)
0000000000000000
10 01234567891112131415
1 = Condition True
0 = Condition False
x = Reserved
Bit #
DigIn CctA
DigIn CctB
DigIn CctC
Bipolr Cct
MtrTyp Cct
NP Hz Cct
MaxFrq Cct
VHz NegSlope
IR Vlts Rang
FlxAmps Rang
SpdRef Cct
Ixo Vlt Rang
Sleep Cong
TB Ref Cct
PTC Conict
Brk Slipped
0000xxxxxxxxxxxx
26 161718192021222324252728293031
1 = Condition True
0 = Condition False
x = Reserved
Bit #
TrqPrv Cct
ProfStpCct
UserSetCct
PICfgCct