User Manual

50 Rockwell Automation Publication 20B-UM002G-EN-P - July 2014
Chapter 1 Programming and Parameters
UTILITY
Diagnostics
222 [Drive Status 3] Read Only
Indicates if a device has manual control of the speed reference or if a “Fast Brake” is in progress.
Option Descriptions
Manual Mode Refer to Manual Speed Sources in the Installation Instructions, publication
20B-IN014
or 20B-IN019.
Fast Braking Fast braking active, see [Stop/Brk Mode A].
223 [Status 3 @ Fault] Read Only
Captures and displays [Drive Status 3] bit pattern at the time of the last fault.
222
224 [Fault Speed]
Captures and displays the output speed of the
drive at the time of the last fault.
Default:
Min/Max:
Units:
Read Only
0.0/+[Maximum Freq]
0.0/+[Maximum Speed]
0.1 Hz
0.1 RPM
079
225
230
225 [Fault Amps]
Captures and displays motor amps at the time of
the last fault.
Default:
Min/Max:
Units:
Read Only
0.0/[Rated Amps] x 2
0.1 Amps
224
230
226 [Fault Bus Volts]
Captures and displays the DC bus voltage of the
drive at the time of the last fault.
Default:
Min/Max:
Units:
Read Only
0.0/Max Bus Volts
0.1 VDC
224
230
227 [Status 1 @ Fault]
Captures and displays [Drive Status 1] bit pattern at the time of
the last fault.
Read Only 209
224
230
228 [Status 2 @ Fault]
Captures and displays [Drive Status 2] bit pattern at the time of
the last fault.
Read Only 210
224
230
File
Group
No.
Parameter Name & Description
See page 16 for symbol descriptions
Values
Related
v6
0xx 0xxxxxxxxxxxx
10 01234567891112131415
1 = Condition True
0 = Condition False
x = Reserved
Bit #
Manual Mode
Fast Braking
v6
0xx 0xxxxxxxxxxxx
10 01234567891112131415
1 = Condition True
0 = Condition False
x = Reserved
Bit #
Manual Mode
Fast Braking
0110000101110000
10 01234567891112131415
1 = Condition True
0 = Condition False
x = Reserved
Bit #
Ready
Active
Command Dir
Actual Dir
Accelerating
Decelerating
Alarm
Faulted
At Speed
Local ID 0
Local ID 1
Local ID 2
Spd Ref ID 0
Spd Ref ID 1
Spd Ref ID 2
Spd Ref ID 3
0000000000000000
10 01234567891112131415
1 = Condition True
0 = Condition False
x = Reserved
Bit #
Ready
Active
Running
Jogging
Stopping
DC Braking
AutoTuning
DB Active
AutoRst Ctdn
AutoRst Act
Curr Limit
Bus Freq Reg
Motor Overld
DPI at 500 k
AdjVltAutoTn
PTC HW