Rockwell Automation Publication 20B-UM002G-EN-P - July 2014 45
Programming and Parameters Chapter 1
UTILITY
MOP Config
194 [Save MOP Ref]
Enables/disables the feature that saves the present MOP frequency reference at power down or at
stop.
195 [MOP Rate]
Sets rate of change of the MOP reference in
response to a digital input.
Default:
Min/Max:
Units:
1.0 Hz/s
30.0 RPM/s
0.2/[Maximum Freq]
6.0/[Maximum Freq]
0.1 Hz/s
0.1 RPM/s
Drive Memory
196 [Param Access Lvl]
Selects the parameter display level viewable on
the HIM.
Basic = Reduced parameter set
Advanced = Full parameter set
Reserved = Full parameter set and
Engineering parameters (refer to the
PowerFlex Reference Manual).
This parameter is not reset when “Reset to
Defaults” is selected.
Default:
Options:
0
0
1
2
“Basic”
“Basic”
“Ad va nc ed ”
“Reserved”
197 [Reset To Defalts]
Resets parameters to factory defaults except [Mtr
NP Pwr Units], [Speed Units], [Param Access Lvl],
[Language], [Voltage Class] & [TorqProve Cnfg]
(params 46, 79, 196, 201, 202 & 600).
Option 1 resets parameters to factory defaults
based on [Voltage Class].
Options 2 & 3 will set [Voltage Class] to low or
high and reset parameters to corresponding
factory defaults.
Important: Frames 5 & 6 - the internal fan
voltage may have to be changed when using
Option 2 or 3. See “Selecting /Verifying Fan
Voltage” in the Installation Instructions,
publication 20B-IN0019
.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“Factory
“Low Voltage
“High Voltage
041
047
054
055
062
063
069
072
082
148
158
198 [Load Frm Usr Set]
Loads a previously saved set of parameter values
from a selected user set location in drive
nonvolatile memory to active drive memory.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“User Set 1”
“User Set 2”
“User Set 3”
199
199 [Save To User Set]
Saves the parameter values in active drive
memory to a user set in drive nonvolatile
memory.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“User Set 1”
“User Set 2”
“User Set 3”
198
200 [Reset Meters]
Resets selected meters to zero.
Default:
Options:
0
0
1
2
“Ready”
“Ready”
“MWh”
“Elapsed Time
File
Group
No.
Parameter Name & Description
See page 16 for symbol descriptions
Values
Related
0xx 0xxxxxxxxxxxx
10 01234567891112131415
1 = Save
0 = Do Not Save
x = Reserved
Bit #
Factory Default Bit Values
At Powr Down
At Stop